| Main |
| Range of product |
Altivar Process ATV600 |
| Product or component type |
Variable speed drive |
| Product specific application |
Process and utilities |
| Device short name |
ATV650 |
| variant |
With disconnect switch |
| product destination |
Asynchronous motors |
| Synchronous motors |
| EMC filter |
Integrated with 50 m conforming to IEC 61800-3 category C2 |
| Integrated with 150 m conforming to IEC 61800-3 category C3 |
| IP degree of protection |
IP55 conforming to IEC 60529 |
| IP55 conforming to IEC 61800-5-1 |
| [Us] rated supply voltage |
380…480 V |
| Type of cooling |
Forced convection |
| Supply frequency |
50…60 Hz – 5…5 % |
| [Us] rated supply voltage |
380…480 V – 15…10 % |
| Motor power kW |
22 kW (heavy duty) |
| 30 kW (normal duty) |
| Motor power hp |
30 hp heavy duty |
| 40 hp normal duty |
| Line current |
45.9 A at 480 V (normal duty) |
| 40.5 A at 380 V (heavy duty) |
| 35.8 A at 480 V (heavy duty) |
| 53.3 A at 380 V (normal duty) |
| Prospective line Isc |
50 kA |
| Apparent power |
29.8 kVA at 480 V (heavy duty) |
| 38.2 kVA at 480 V (normal duty) |
| Continuous output current |
59 A at 4 kHz for normal duty |
| 46.3 A at 4 kHz for heavy duty |
| Asynchronous motor control profile |
Optimized torque mode |
| Constant torque standard |
| Variable torque standard |
| Synchronous motor control profile |
Synchronous reluctance motor |
| Permanent magnet motor |
| Speed drive output frequency |
0.1…500 Hz |
| Nominal switching frequency |
4 kHz |
| Switching frequency |
4…12 kHz with derating factor |
| 2…12 kHz adjustable |
| Safety function |
STO (safe torque off) SIL 3 |
| Discrete input logic |
16 preset speeds |
| Communication port protocol |
Ethernet |
| Modbus serial |
| Modbus serial |
| Option card |
Slot A: communication module, PROFINET |
| Slot A: communication module, DeviceNet |
| Slot A: communication module, Modbus TCP/EtherNet/IP |
| Slot A: communication module, CANopen daisy chain RJ45 |
| Slot A: communication module, CANopen SUB-D 9 |
| Slot A: communication module, CANopen screw terminals |
| Slot A/slot B: digital and analog I/O extension module |
| Slot A/slot B: output relay extension module |
| Slot A: communication module, Ethernet IP/Modbus TCP/MD-Link |
| Communication module, BACnet MS/TP |
| Communication module, Ethernet Powerlink |
| Slot A: communication module, Profibus DP V1 |
| Complementary |
| mounting mode |
Wall mount |
| Maximum transient current |
69.5 A during 60 s (normal duty) |
| 67.7 A during 60 s (heavy duty) |
| Network number of phases |
3 phases |
| Discrete output number |
0 |
| Discrete output type |
Relay outputs R1A, R1B, R1C 250 V AC 3000 mA |
| Relay outputs R1A, R1B, R1C 30 V DC 3000 mA |
| Relay outputs R2A, R2C 250 V AC 5000 mA |
| Relay outputs R2A, R2C 30 V DC 5000 mA |
| Relay outputs R3A, R3C 250 V AC 5000 mA |
| Relay outputs R3A, R3C 30 V DC 5000 mA |
| Output voltage |
<= power supply voltage |
| Permissible temporary current boost |
1.5 x In during 60 s (heavy duty) |
| 1.1 x In during 60 s (normal duty) |
| Motor slip compensation |
Automatic whatever the load |
| Can be suppressed |
| Not available in permanent magnet motor law |
| Can be suppressed |
| Acceleration and deceleration ramps |
Linear adjustable separately from 0.01…9999 s |
| Physical interface |
Ethernet |
| 2-wire RS 485 |
| Braking to standstill |
By DC injection |
| Protection type |
Safe torque off: motor |
| Motor phase break: motor |
| Thermal protection: drive |
| Safe torque off: drive |
| Overheating: drive |
| Overcurrent between output phases and earth: drive |
| Overload of output voltage: drive |
| Short-circuit protection: drive |
| Motor phase break: drive |
| Overvoltages on the DC bus: drive |
| Line supply overvoltage: drive |
| Line supply undervoltage: drive |
| Line supply phase loss: drive |
| Overspeed: drive |
| Break on the control circuit: drive |
| Thermal protection: motor |
| Transmission rate |
10, 100 Mbits |
| 4800 bps, 9600 bps, 19200 bps, 38.4 Kbps |
| Frequency resolution |
Analog input: 0.012/50 Hz |
| Display unit: 0.1 Hz |
| Transmission frame |
RTU |
| Electrical connection |
Line side: screw terminal 25…50 mm²/AWG 4…AWG 1 |
| Motor: screw terminal 25…50 mm²/AWG 4…AWG 1 |
| Control: removable screw terminals 0.5…1.5 mm² |
| Connector type |
RJ45 (on the remote graphic terminal) for Modbus serial |
| RJ45 (on the remote graphic terminal) for Ethernet/Modbus TCP |
| Data format |
8 bits, configurable odd, even or no parity |
| Type of polarization |
No impedance |
| Exchange mode |
Half duplex, full duplex, autonegotiation Ethernet/Modbus TCP |
| Number of addresses |
1…247 for Modbus serial |
| Method of access |
Slave Modbus TCP |
| Supply |
Internal supply for reference potentiometer (1 to 10 kOhm): 10.5 V DC +/- 5 %, <10 mA, protection type: overload and short-circuit protection |
| Internal supply for digital inputs and STO: 24 V DC (21…27 V), <200 mA, protection type: overload and short-circuit protection |
| External supply for digital inputs: 24 V DC (19…30 V), <1.25 mA, protection type: overload and short-circuit protection |
| Local signalling |
3 LEDs (dual colour) for embedded communication status |
| 4 LEDs (dual colour) for communication module status |
| 1 LED (red) for presence of voltage |
| 3 LEDs for local diagnostic |
| Width |
290 mm |
| Height |
910 mm |
| Depth |
401 mm |
| Net weight |
50 kg |
| Analogue input number |
3 |
| Analogue input type |
AI1, AI2, AI3 software-configurable voltage: 0…10 V DC, impedance: 31.5 kOhm, resolution 12 bits |
| AI1, AI2, AI3 software-configurable current: 0…20 mA, impedance: 250 Ohm, resolution 12 bits |
| AI2 voltage analog input: – 10…10 V DC, impedance: 31.5 kOhm, resolution 12 bits |
| Discrete input number |
8 |
| Discrete input type |
DI7, DI8 programmable as pulse input: 0…30 kHz, 24 V DC (<= 30 V) |
| Input compatibility |
DI5, DI6: discrete input level 1 PLC conforming to IEC 65A-68 |
| STOA, STOB: discrete input level 1 PLC conforming to IEC 61131-2 |
| DI1…DI6: discrete input level 1 PLC conforming to IEC 61131-2 |
| Discrete input logic |
Positive logic (source) (DI1…DI8), < 5 V (state 0), > 11 V (state 1) |
| Negative logic (sink) (DI1…DI8), > 16 V (state 0), < 10 V (state 1) |
| Analogue output number |
2 |
| Analogue output type |
Software-configurable voltage AQ1, AQ2: 0…10 V DC impedance 470 Ohm, resolution 10 bits |
| Software-configurable current AQ1, AQ2: 0…20 mA, resolution 10 bits |
| Software-configurable current DQ-, DQ+: 30 V DC |
| Software-configurable current DQ-, DQ+: 100 mA |
| Sampling duration |
5 ms +/- 1 ms (DI5, DI6) – discrete input |
| 5 ms +/- 0.1 ms (AI1, AI2, AI3) – analog input |
| 10 ms +/- 1 ms (AO1) – analog output |
| 2 ms +/- 0.5 ms (DI1…DI4) – discrete input |
| Accuracy |
+/- 1 % AO1, AO2 for a temperature variation 60 °C analog output |
| +/- 0.6 % AI1, AI2, AI3 for a temperature variation 60 °C analog input |
| Linearity error |
AO1, AO2: +/- 0.2 % for analog output |
| AI1, AI2, AI3: +/- 0.15 % of maximum value for analog input |
| Relay output number |
3 |
| Relay output type |
Configurable relay logic R2: sequence relay NO electrical durability 100000 cycles |
| Configurable relay logic R3: sequence relay NO electrical durability 100000 cycles |
| Configurable relay logic R1: fault relay NO/NC electrical durability 100000 cycles |
| Refresh time |
Relay output (R1, R2, R3): 5 ms (+/- 0.5 ms) |
| Minimum switching current |
Relay output R1, R2, R3: 5 mA at 24 V DC |
| Maximum switching current |
Relay output R1, R2, R3 on resistive load, cos phi = 1: 3 A at 30 V DC |
| Relay output R1, R2, R3 on inductive load, cos phi = 0.4 and L/R = 7 ms: 2 A at 250 V AC |
| Relay output R1, R2, R3 on inductive load, cos phi = 0.4 and L/R = 7 ms: 2 A at 30 V DC |
| Relay output R1, R2, R3 on resistive load, cos phi = 1: 3 A at 250 V AC |
| Isolation |
Between power and control terminals |
| Maximum output frequency |
500 kHz |
| Maximum input current |
53.3 A |
| Variable speed drive application selection |
Food and beverage processing other application |
| Mining mineral and metal fan |
| Mining mineral and metal pump |
| Oil and gas fan |
| Water and waste water other application |
| Building – HVAC screw compressor |
| Food and beverage processing pump |
| Food and beverage processing fan |
| Food and beverage processing atomization |
| Oil and gas electro submersible pump (ESP) |
| Oil and gas water injection pump |
| Oil and gas jet fuel pump |
| Oil and gas compressor for refinery |
| Water and waste water centrifuge pump |
| Water and waste water positive displacement pump |
| Water and waste water electro submersible pump (ESP) |
| Water and waste water screw pump |
| Water and waste water lobe compressor |
| Water and waste water screw compressor |
| Water and waste water compressor centrifugal |
| Water and waste water fan |
| Water and waste water conveyor |
| Water and waste water mixer |
| Motor power range AC-3 |
30…50 kW at 480…500 V 3 phases |
| Quantity per set |
1 |
| enclosure mounting |
Wall mounted |
| Environment |
| Insulation resistance |
> 1 MOhm 500 V DC for 1 minute to earth |
| Noise level |
69.7 dB conforming to 86/188/EEC |
| Operating position |
Vertical +/- 10 degree |
| Maximum THDI |
<48 % from 80…100 % of load conforming to IEC 61000-3-12 |
| Electromagnetic compatibility |
Radiated radio-frequency electromagnetic field immunity test level 3 conforming to IEC 61000-4-3 |
| Electrical fast transient/burst immunity test level 4 conforming to IEC 61000-4-4 |
| 1.2/50 µs – 8/20 µs surge immunity test level 3 conforming to IEC 61000-4-5 |
| Conducted radio-frequency immunity test level 3 conforming to IEC 61000-4-6 |
| Electrostatic discharge immunity test level 3 conforming to IEC 61000-4-2 |
| Pollution degree |
2 conforming to IEC 61800-5-1 |
| Vibration resistance |
1 gn (f= 13…200 Hz) conforming to IEC 60068-2-6 |
| 1.5 mm peak to peak (f= 2…13 Hz) conforming to IEC 60068-2-6 |
| Shock resistance |
15 gn for 11 ms conforming to IEC 60068-2-27 |
| Relative humidity |
5…95 % without condensation conforming to IEC 60068-2-3 |
| Ambient air temperature for operation |
40…50 °C (with derating factor) |
| -15…40 °C (without derating) |
| ambient air temperature for storage |
-40…70 °C |
| Operating altitude |
1000…4800 m with current derating 1 % per 100 m |
| <= 1000 m without derating |
| Product certifications |
TÜV |
| DNV-GL |
| UL |
| ATEX zone 2/22 |
| ATEX INERIS |
| Marking |
CE |
| Standards |
IEC 61800-3 |
| IEC 61800-3 environment 1 category C2 |
| EN/IEC 61800-3 environment 2 category C3 |
| IEC 61800-5-1 |
| IEC 61000-3-12 |
| IEC 60721-3 |
| IEC 61508 |
| IEC 13849-1 |
| Overvoltage category |
III |
| Regulation loop |
Adjustable PID regulator |
| Noise level |
69.7 dB |
| Pollution degree |
3 |