| Main |
| Device short name |
ATV212 |
| Product destination |
Asynchronous motors |
| Phase |
3 phase |
| Motor power kW |
18.5 kW |
| Maximum Horse Power Rating |
25 hp |
| Supply voltage limits |
323…528 V |
| Supply frequency |
50…60 Hz – 5…5 % |
| Line current |
27.8 A 480 V |
| 34.8 A 380 V |
| Range of Product |
Altivar 212 |
| Product or Component Type |
Variable speed drive |
| Product Specific Application |
Pumps and fans in HVAC |
| Communication Port Protocol |
APOGEE FLN |
| BACnet |
| LonWorks |
| Modbus |
| METASYS N2 |
| [Us] rated supply voltage |
380…480 V – 15…10 % |
| EMC filter |
Class C2 EMC filter integrated |
| IP degree of protection |
IP21 |
| Complementary |
| Apparent power |
28.2 kVA 380 V |
| Continuous output current |
37 A 380 V |
| 37 A 460 V |
| Maximum transient current |
40.7 A 60 s |
| Speed drive output frequency |
0.5…200 Hz |
| Speed range |
1…10 |
| Speed accuracy |
+/- 10 % of nominal slip 0.2 Tn to Tn |
| Local signalling |
for DC bus energized 1 LED (red) |
| Output voltage |
<= power supply voltage |
| Isolation |
Electrical between power and control |
| Type of cable |
Without mounting kit 1 IEC cable 113 °F (45 °C), copper 90 °C / XLPE/EPR |
| Without mounting kit 1 IEC cable 113 °F (45 °C), copper 70 °C / PVC |
| With UL Type 1 kit 3 UL 508 cable 104 °F (40 °C), copper 75 °C / PVC |
| Electrical connection |
VIA, VIB, FM, FLA, FLB, FLC, RY, RC, F, R, RES terminal 0.004 in² (2.5 mm²) / AWG 14 |
| L1/R, L2/S, L3/T terminal 0.04 in² (25 mm²) / AWG 3 |
| Tightening torque |
5.3 lbf.in (0.6 N.m) VIA, VIB, FM, FLA, FLB, FLC, RY, RC, F, R, RES) |
| 39.8 lbf.in (4.5 N.m), 40 lb.in L1/R, L2/S, L3/T) |
| Supply |
Internal supply for reference potentiometer (1 to 10 kOhm) 10.5 V DC +/- 5 %, <10 A overload and short-circuit protection |
| Internal supply 24 V DC 21…27 V), <200 A overload and short-circuit protection |
| Sampling duration |
2 ms +/- 0.5 ms F discrete |
| 2 ms +/- 0.5 ms R discrete |
| 2 ms +/- 0.5 ms RES discrete |
| 3.5 ms +/- 0.5 ms VIA analog |
| 22 ms +/- 0.5 ms VIB analog |
| Response time |
FM 2 ms +/- 0.5 ms analog |
| FLA, FLC 7 ms +/- 0.5 ms discrete |
| FLB, FLC 7 ms +/- 0.5 ms discrete |
| RY, RC 7 ms +/- 0.5 ms discrete |
| Accuracy |
+/- 0.6 % VIA) for a temperature variation 60 °C |
| +/- 0.6 % VIB) for a temperature variation 60 °C |
| +/- 1 % FM) for a temperature variation 60 °C |
| Linearity error |
VIA +/- 0.15 % of maximum value input |
| VIB +/- 0.15 % of maximum value input |
| FM +/- 0.2 % output |
| Analogue output type |
FM switch-configurable voltage 0…10 V DC 7620 Ohm 10 bits |
| FM switch-configurable current 0…20 mA 970 Ohm 10 bits |
| Discrete output type |
Configurable relay logic FLA, FLC) NO – 100000 cycles |
| Configurable relay logic FLB, FLC) NC – 100000 cycles |
| Configurable relay logic RY, RC) NO – 100000 cycles |
| Minimum switching current |
3 mA 24 V DC configurable relay logic |
| Maximum switching current |
5 A 250 V AC resistive cos phi = 1 L/R = 0 ms FL, R) |
| 5 A 30 V DC resistive cos phi = 1 L/R = 0 ms FL, R) |
| 2 A 250 V AC inductive cos phi = 0.4 L/R = 7 ms FL, R) |
| 2 A 30 V DC inductive cos phi = 0.4 L/R = 7 ms FL, R) |
| Discrete input type |
F programmable 24 V DC level 1 PLC 4700 Ohm |
| R programmable 24 V DC level 1 PLC 4700 Ohm |
| RES programmable 24 V DC level 1 PLC 4700 Ohm |
| Discrete input logic |
Positive logic (source) F, R, RES), <= 5 V, >= 11 V |
| Negative logic (sink) F, R, RES), >= 16 V, <= 10 V |
| Dielectric strength |
3535 V DC between earth and power terminals |
| 5092 V DC between control and power terminals |
| Insulation resistance |
>= 1 mOhm 500 V DC for 1 minute |
| Frequency resolution |
Display unit 0.1 Hz |
| Analog input 0.024/50 Hz |
| communication service |
Time out setting from 0.1 to 100 s |
| Read device identification (43) |
| Monitoring inhibitable |
| Read holding registers (03) 2 words maximum |
| Write multiple registers (16) 2 words maximum |
| Write single register (06) |
| Option card |
Communication card LonWorks |
| Power dissipation in W |
603 W |
| Air flow |
56533.8 Gal/hr(US) (214 m3/h) |
| Functionality |
Mid |
| Specific application |
HVAC |
| Variable speed drive application selection |
Building – HVAC compressor for scroll |
| Building – HVAC fan |
| Building – HVAC pump |
| Motor power range AC-3 |
15…25 kW 380…440 V 3 phase |
| 15…25 kW 480…500 V 3 phase |
| Motor starter type |
Variable speed drive |
| Discrete output number |
2 |
| Analogue input number |
2 |
| Analogue input type |
VIA switch-configurable voltage 0…10 V DC 24 V max 30000 Ohm 10 bits |
| VIB configurable voltage 0…10 V DC 24 V max 30000 Ohm 10 bits |
| VIB configurable PTC probe 0…6 probes 1500 Ohm |
| VIA switch-configurable current 0…20 mA 250 Ohm 10 bits |
| Analogue output number |
1 |
| Physical interface |
2-wire RS 485 |
| Connector Type |
1 open style |
| 1 RJ45 |
| Transmission Rate |
9600 bps or 19200 bps |
| Transmission frame |
RTU |
| Number of addresses |
1…247 |
| Data format |
8 bits, 1 stop, odd even or no configurable parity |
| Type of polarization |
No impedance |
| Asynchronous motor control profile |
Voltage/frequency ratio, 5 points |
| Voltage/frequency ratio – Energy Saving, quadratic U/f |
| Voltage/frequency ratio, 2 points |
| Voltage/frequency ratio, automatic IR compensation (U/f + automatic Uo) |
| Flux vector control without sensor, standard |
| Torque accuracy |
+/- 15 % |
| Transient overtorque |
120 % of nominal motor torque +/- 10 % 60 s |
| Acceleration and deceleration ramps |
Linear adjustable separately from 0.01 to 3200 s |
| Automatic based on the load |
| Motor slip compensation |
Not available in voltage/frequency ratio motor control |
| Automatic whatever the load |
| Adjustable |
| Switching frequency |
6…16 kHz adjustable |
| 8…16 kHz with derating factor |
| Nominal switching frequency |
8 kHz |
| Braking to standstill |
By DC injection |
| Network Frequency |
47.5…63 Hz |
| Prospective line Isc |
22 kA |
| Protection type |
Overheating protection drive |
| Thermal power stage drive |
| Short-circuit between motor phases drive |
| Input phase breaks drive |
| Overcurrent between output phases and earth drive |
| Overvoltages on the DC bus drive |
| Break on the control circuit drive |
| Against exceeding limit speed drive |
| Line supply overvoltage and undervoltage drive |
| Line supply undervoltage drive |
| Against input phase loss drive |
| Thermal protection motor |
| Motor phase break motor |
| With PTC probes motor |
| Width |
9.6 in (245 mm) |
| Height |
13.0 in (330 mm) |
| Depth |
7.5 in (190 mm) |
| Net Weight |
25.68 lb(US) (11.65 kg) |
| Environment |
| Pollution degree |
2 IEC 61800-5-1 |
| IP degree of protection |
IP20 on upper part without blanking plate on cover IEC 61800-5-1 |
| IP20 on upper part without blanking plate on cover IEC 60529 |
| IP21 IEC 61800-5-1 |
| IP21 IEC 60529 |
| IP41 on upper part IEC 61800-5-1 |
| IP41 on upper part IEC 60529 |
| Vibration resistance |
1.5 mm 3…13 Hz)IEC 60068-2-6 |
| 1 gn 13…200 Hz)EN/IEC 60068-2-8 |
| Shock resistance |
15 gn 11 ms IEC 60068-2-27 |
| Environmental characteristic |
Classes 3C1 IEC 60721-3-3 |
| Classes 3S2 IEC 60721-3-3 |
| Noise level |
54 dB 86/188/EEC |
| Operating altitude |
3280.84…9842.52 ft (1000…3000 m) limited to 2000 m for the Corner Grounded distribution network with current derating 1 % per 100 m |
| <= 3280.84 ft (1000 m) without derating |
| Relative humidity |
5…95 % without condensation IEC 60068-2-3 |
| 5…95 % without dripping water IEC 60068-2-3 |
| Ambient air temperature for operation |
14…104 °F (-10…40 °C) without derating) |
| 104…122 °F (40…50 °C) with derating factor) |
| Operating position |
Vertical +/- 10 degree |
| Product Certifications |
CSA |
| UL |
| C-tick |
| NOM 117 |
| marking |
CE |
| Standards |
IEC 61800-3 environments 1 category C2 |
| IEC 61800-3 category C2 |
| IEC 61800-3 |
| IEC 61800-3 environments 1 category C1 |
| IEC 61800-5-1 |
| IEC 61800-3 environments 2 category C1 |
| IEC 61800-3 environments 2 category C2 |
| IEC 61800-3 environments 1 category C2 |
| EN 55011 class A group 1 |
| IEC 61800-3 environments 1 category C3 |
| IEC 61800-3 environments 1 category C3 |
| IEC 61800-3 |
| IEC 61800-3 category C3 |
| EN 61800-3 category C3 |
| IEC 61800-3 category C2 |
| IEC 61800-5-1 |
| UL Type 1 |
| IEC 61800-3 environments 2 category C3 |
| IEC 61800-3 environments 1 category C1 |
| IEC 61800-3 environments 2 category C2 |
| IEC 61800-3 environments 2 category C3 |
| IEC 61800-3 environments 2 category C1 |
| Assembly style |
With heat sink |
| Electromagnetic compatibility |
Electrostatic discharge immunity test level 3 IEC 61000-4-2 |
| Radiated radio-frequency electromagnetic field immunity test level 3 IEC 61000-4-3 |
| Electrical fast transient/burst immunity test level 4 IEC 61000-4-4 |
| 1.2/50 µs – 8/20 µs surge immunity test level 3 IEC 61000-4-5 |
| Conducted radio-frequency immunity test level 3 IEC 61000-4-6 |
| Voltage dips and interruptions immunity test IEC 61000-4-11 |
| Regulation loop |
Adjustable PI regulator |
| Ambient Air Temperature for Storage |
-13…158 °F (-25…70 °C) |
| Ordering and shipping details |
| Category |
US1CP4D22157 |
| Discount Schedule |
CP4D |
| GTIN |
3606480322532 |
| Returnability |
Yes |
| Country of origin |
US |