Such: Siemens 6SL3120... ...

Sales03@aotewell.com
Mob/WhatsAPP: +86-133-6088-4385

6SL3320-1TE32-1AA3 SINAMICS S120 600 V DC OUTPUT: 3-PH 400 V

Part Number: 6SL3320-1TE32-1AA3
Manufacturer Brands: SIEMENS
Place of Originr: Made in Germany
Net Weight: 88.000 Kg

Inquire this item

EurAutomation.com is a professional supplier of industrial automation products, providing integrated solutions, such as PLC, HMI, CNC, DRIVES, CNC, INVERTER, VFDs, frequency converter cabinet, DC speed control cabinet, widely used in industrial automation, process automation, humanoid robots, intelligent factories, unmanned workshops, no matter what your procurement needs are, you only need to send an email. We will serve you as soon as possible.

6SL3320-1TE32-1AA3 Detailed English Specifications (Siemens SINAMICS S120 Single Motor Module)

This is a chassis – mounted, air – cooled single motor module for the Siemens SINAMICS S120 converter system, which is applicable to 3 – phase industrial drive scenarios, and supports extended safety – integrated functions, with a rated output current of 210A and a rated power of 150kW (based on IN at 400V 3AC). The detailed parameter tables are as follows:

Basic Identification

Item Details
Part Number 6SL3320-1TE32-1AA3
Product Type SINAMICS S120 Single Motor Module
Manufacturer Siemens
Application Industrial 3 – phase AC drives, compatible with servo/V/f/vector control
Mounting Type Chassis – mounted
Cooling Method Internal forced air cooling
Protection Class IP20
Net Weight Approx. 95 kg
RoHS Compliance Yes
Communication Interface DRIVE – CLiQ (incl. cable)
Safety Functions Extended Safety Integrated (e.g., STO, SS1, SS2)

Electrical Specifications (Core)

Parameter Value Unit Remarks
DC Link Input Voltage 510-750 (nominal 600) V DC Working voltage range
DC Link Rated Current (IN DC) 252 (Basic/Smart Line Module); 227 (Active Line Module) A Rated current matching different line modules
DC Link Base – load Current (IL DC) 245 (Basic/Smart Line Module); 221 (Active Line Module) A Continuous base – load current
DC Link Base – load Current (IH DC) 224 (Basic/Smart Line Module); 202 (Active Line Module) A High – temperature base – load current
Rated Output Current (IN) 210 A 3 – phase AC output, 400V, 50/60Hz
Base – load Output Current (IL) 205 A Continuous base – load output current
High – temp Base – load Output Current (IH) 178 A Output current under high – temperature base – load
S6 Duty (40%) Current (IS6) 230 A Short – term overload (40% duty cycle)
Rated Output Power (IN – based) 150 kW At 400V 3AC, 50Hz
Rated Output Power (IH – based) 90 kW At 400V 3AC, 50Hz
Output Voltage 0.0-0.75 × DC link voltage (max. 400) V AC (3 – phase) Proportional to DC link input
Output Frequency 0-550 Hz For servo/V/f/vector control
Rated Switching Frequency 2.0 kHz Fixed max. 2.0 kHz
DC Link Capacitance 4,200 µF Filtering and energy storage
Control Voltage 24 (-15%/+20%) V DC Auxiliary power supply, current consumption 0.63A at 400V AC
Insulation Voltage 1080 V AC (1 min) Dielectric strength test value

Thermal & Environmental

Parameter Value Unit Derating/Notes
Operating Temperature (No Derating) 0-40 °C Continuous operation
Operating Temperature (Derating) 40-60 °C Linear derating applies
Storage Temperature -25-70 °C No condensation allowed
Relative Humidity 5-95 % Non – condensing, no corrosive gases
Altitude (No Derating) ≤1000 m Standard condition
Altitude (Derating) >1000 m 1% derating per 100m above 1000m
Vibration Resistance 5-150Hz, 0.5 g Compliant with IEC 60068-2-6
Shock Resistance 10g, 11 ms Compliant with IEC 60068-2-27
Sound Pressure Level (1m) 71 dB (50/60Hz) Typical operation noise

Power Loss & Protection

Parameter Value Unit Remarks
Max. Power Loss Approx. 2.5 kW At 400V, 50Hz, full load
Short – Circuit Protection Internal fast – acting fuses Compliant with IEC 60947-4-1
Overvoltage Protection DC link varistor + active clamping Triggers at ~780V DC
Overcurrent Protection Electronic current limiting (up to 307A peak) A Protects power devices