Product Type: Power Module PM240-2 | Status: Active | Core Features: Built-in Class A EMC filter + built-in braking chopper | Input: 3AC 380–480 V, 47–63 Hz | Output: 3AC 0–480 V, 0–550 Hz | Rated Power: 110 kW (Low Overload, LO) / 90 kW (High Overload, HO) | Protection: IP20 (open chassis)
1. Electrical Ratings
| Parameter | Value | Notes |
|---|---|---|
| Line Voltage (3AC) | 380 … 480 V AC (+10% / -20%) | 47–63 Hz |
| Output Voltage | 0 … 480 V AC | Symmetrical to input |
| Output Frequency | 0 … 550 Hz | Max. carrier frequency dependent on load |
| Low Overload (LO) – 40°C ambient | ||
| Rated Output Power (Pₙ) | 110 kW | 100% duty, 110% 57s, 150% 3s |
| Rated Output Current (Iₙ) | 205 A | Continuous |
| Max. Peak Current | 356 A | Short-term (3s) |
| High Overload (HO) – 50°C ambient | ||
| Rated Output Power (Pₙ) | 90 kW | 100% duty, 150% 57s, 200% 3s |
| Rated Output Current (Iₙ) | 178 A | Continuous |
| Braking Chopper | Built-in | For dynamic braking (external resistor required) |
| EMC Filter | Built-in Class A | Complies with IEC 61800-3 |
| 24 V DC Aux Supply | 24 V DC (-15% / +20%) | 20.4–28.8 V DC, max 0.5 A |
| Power Loss (Typ.) | ~1.8 kW | At rated LO load (110 kW) |
| Insulation Class | F (155 °C) | |
| Dielectric Test Voltage | 3.0 kV AC (1 min) | Line/output/aux to ground |
| Safety Integrated | STO (Safe Torque Off) | SIL 2 (IEC 61508), PL d (EN ISO 13849-1), Cat. 3 |
2. Mechanical & Environmental Data
| Parameter | Value | Notes |
|---|---|---|
| Dimensions (H×W×D) | 708 mm × 305 mm × 357 mm | 27.87 × 12.01 × 14.06 in |
| Net Weight | 79 kg | 174.16 lb |
| Degree of Protection | IP20 (front), IP00 (rear) | Forced-air cooled |
| Cooling | Forced-air (internal fans) | Air flow optimized for cabinet mounting |
| Ambient Temp (Operation) | -20 … +40 °C (LO) / -20 … +50 °C (HO) | Derate above 40/50 °C |
| Storage Temperature | -40 … +85 °C | |
| Installation Altitude (No Derating) | ≤ 1000 m | 1% derate per 100 m above 1000 m |
| Humidity | 5 … 95% RH | Non-condensing |
| Terminals (Line/Output) | M12 bolt | Conductor cross-section: 95 … 185 mm² (2/0 … 350 MCM) |
| PE Connection | M12 screw | Low-impedance ground required |
| Max. Motor Cable Length | Shielded: 100 m; Unshielded: 150 m | With built-in filter; extend with output reactor |
3. Key Features & Standards
- Modular Design: Works with G120 Control Units (CU240B/E-2, CU250S-2)
- Built-in Filter & Chopper: Reduces cabinet space, simplifies wiring
- Overload & Thermal Protection: I²t motor protection, overtemperature shutdown
- EMC Compliance: CE, cULus, RCM (C-Tick), SEMI F47, RoHS
- Communication: DRIVE-CLiQ (to CU), STO, digital I/O, braking resistor interface
- Firmware: Compatible with CU V4.7 HF8 and later
4. Installation & Application Notes
- Mount vertically (top/bottom airflow) in a ventilated cabinet; clearances per Siemens manual
- Derate for high altitude, high ambient temp, or continuous overload
- Braking resistor sizing: use Siemens G120 sizing tool for dynamic braking
- Use shielded motor cable for EMC; bond shield at both ends
- Match to CU with matching firmware version; update if needed
- Technical data subject to change; always verify with latest official docs