Such: Siemens 6SL3120... ...

Sales03@aotewell.com
Mob/WhatsAPP: +86-133-6088-4385

ACS800-04-2120-7+E205+V991 CONVERTER 690V 1774A 1700KW

Part Number: ACS800-04-2120-7+E205+V991
Manufacturer Brands: SIEMENS
Place of Originr: Made in Finland

Inquire this item

EurAutomation.com is a professional supplier of industrial automation products, providing integrated solutions, such as PLC, HMI, CNC, DRIVES, CNC, INVERTER, VFDs, frequency converter cabinet, DC speed control cabinet, widely used in industrial automation, process automation, humanoid robots, intelligent factories, unmanned workshops, no matter what your procurement needs are, you only need to send an email. We will serve you as soon as possible.
This is a detailed English parameter sheet for the ABB ACS800‑04‑2120‑7 (single‑drive module) with options E205, V991, covering core electrical ratings, option specs, communication, physical‑environmental data, and compliance for industrial motor control applicationsABB Group.

Core Electrical Ratings

Parameter Value Notes
Input Voltage (U₁) 3AC 525–690 V (50/60 Hz) 7th voltage code; tolerance ±10%
Rated Input Current (I₁ₙ) 2120 A (rms, 3‑phase) At 690 V rated voltage
Rated Output Power (Pₒᵤₜₙ) 1200 kW (at 690 V, 50 Hz) DTC control; 98% nominal efficiency
Rated Output Current (Iₒᵤₜₙ) 2120 A (rms, 3‑phase) Continuous at 40°C ambient
Output Voltage (Uₒᵤₜ) 0–690 V (3‑phase, variable) Matches input voltage range
Output Frequency (fₒᵤₜ) 0–300 Hz (standard); ±300 Hz (optional) Speed/torque control range
DC Link Voltage (U<sub>DC</sub>) ~1000 VDC (unloaded); ~950 VDC (loaded) Diode rectifier output
Overload Capacity 110% Iₙ for 60 s; 150% Iₙ for 1 s Per ABB single‑drive design specs
Power Loss (P<sub>loss</sub>) ~10.5 kW (typical, at rated load) Includes module + option power draw
Auxiliary Supply (Uₐᵤₓ) 24 VDC (19.2–28.8 VDC) Control circuit power
Auxiliary Current (Iₐᵤₓ) 5 A (max) For logic, I/O, and cooling fans

Option Specifications (E205+V991)

Option Type Key Parameters Function
E205 Integrated EMC Filter EN 61800‑3 C2 compliance; 150 kHz–30 MHz attenuation Reduces conducted/radiated emissions
V991 Advanced Protection SW Overvoltage/overcurrent/ground‑fault monitoring; thermal modeling Enhanced drive/motor protection

Communication & Control

Parameter Value Details
Control Method Direct Torque Control (DTC) Speed/torque control without encoder
Digital Inputs 6 (programmable, 24 VDC) 24 VDC, -15% to +20% tolerance
Analog Inputs 3 (0/4–20 mA or 0/2–10 V) 12‑bit resolution; galvanically isolated
Analog Outputs 2 (0/4–20 mA) Max load impedance ≤700 Ω
Relay Outputs 3 (programmable) 8 A at 24 VDC/250 VAC; 0.4 A at 120 VDC
Fieldbus Options Profibus DP, Modbus RTU, CANopen V991 enables remote diagnostics

Physical & Environmental

Parameter Value Limits
Dimensions (H×W×D) 2000 × 600 × 300 mm Cabinet‑mounted profile
Weight 320 kg Steel housing; IP20 rear protection
Protection Class Front: IP00; Rear: IP20 Cabinet‑mount only (indoor use)
Ambient Temp (Operation) 0–40°C Derate 1%/°C above 40°C (max 50°C)
Ambient Temp (Storage) -40–70°C No condensation
Relative Humidity 5–95% (non‑condensing) Operation/storage
Altitude ≤ 1000 m Derate 1%/100 m above 1000 m
Vibration/Shock IEC 60068‑2‑6 (vibration); IEC 60068‑2‑27 (shock) 10–500 Hz, 0.5 g (vibration); 15 g (shock, 11 ms)

Protection & Compliance

Feature Details
Overvoltage Clamping at 1.3×U<sub>DC</sub> Transient surge protection
Overcurrent Electronic current limiting Trips at >150% Iₙ (sustained)
Short‑Circuit Fuse‑protected input (optional) 200 kA SCCR (690 V)
Standards CE, UL 508C, cUL, IEC 61800‑5‑1 Industrial safety/EMC compliance