ACS880-01-293A-3+J425+R700 max: 160kW, Icont.max:293A

Part Number: ACS880-01-293A-3+J425+R700
Manufacturer Brands: SIEMENS
Place of Originr: Made in Germany
Net Weight: 68 kg

Inquire this item

EurAutomation.com is a professional supplier of industrial automation products, providing integrated solutions, such as PLC, HMI, CNC, DRIVES, CNC, INVERTER, VFDs, frequency converter cabinet, DC speed control cabinet, widely used in industrial automation, process automation, humanoid robots, intelligent factories, unmanned workshops, no matter what your procurement needs are, you only need to send an email. We will serve you as soon as possible.

ACS880-01-293A-3+J425+R700 English Technical Parameters (Detailed)

This is a 3-phase wall-mounted industrial AC drive from ABB’s ACS880-01 series, with a rated output power of 160 kW (400 V, 3-phase), a rated output current of 293 A (Normal Duty), equipped with ACS-AP-I Industrial Assistant control panel (J425) and English documentation (R700)ABB Group. The detailed English parameters are as follows:

Core Electrical Parameters

Parameter Specification
Model ACS880-01-293A-3+J425+R700
Product Type LV AC Industrial Wall-Mounted Single Drive (IEC Standard)
Input Voltage (Uin) 3-phase, 380-480 V AC (±10%), 50/60 Hz (47.5-63 Hz allowed)
Input Frequency 47.5-63 Hz
Output Voltage (Uout) 0-Uin (3-phase, 380-480 V AC)
Output Frequency Range 0-500 Hz
Output Current (Normal Duty, In) 293 A
Output Current (Heavy Duty, IHD) 246 A
Output Current (Light Overload, ILD) 278 A
Output Power (Normal Duty, Pn) 160 kW (at 400 V)
Output Power (Heavy Duty, PHD) 132 kW
Output Power (Light Overload, PLD) 160 kW
Number of Phases (Input/Output) 3-phase
Overload Capacity 1.5 × In for 1 min (293 A × 1.5 = 439.5 A, max. 1 min every 5 min); 1.1 × In for continuous operation
Switching Frequency 2-16 kHz (adjustable, default 4 kHz)
Efficiency (at Nominal Power) 98% (approx.)
Power Factor (Fundamental) 0.98
Power Factor (Total) 0.95 (approx., at full load)
Input Reactor Standard (built-in)
Brake Chopper Standard (for frame size R8)

Option Code Definitions (J425+R700)

Option Code Function Description
J425 ACS-AP-I Industrial Assistant control panel (compatible with ACS380, 580, 880; supports parameter setting, monitoring, diagnostics, and maintenance guidance)
R700 Documentation/manuals in English (printed copy and electronic version for quick commissioning and maintenance)

Physical & Installation Parameters

Parameter Specification
Frame Size R8
Mounting Type Wall-mounted (standard); cabinet-assembly (optional)
Protection Class IP21 (standard, wall-mounted); IP55 (optional, for dusty/wet environments)
Enclosure Type NEMA Type 1
Dimensions (H×W×D) 965 mm × 300 mm × 386 mm
Net Weight 68 kg
Cooling Method Forced air cooling (internal fan, 230 V AC fan supply)
Ambient Temperature (Operating) -10°C to +40°C (derate 1%/°C above 40°C, up to 50°C)
Ambient Temperature (Storage) -40°C to +70°C
Altitude ≤1000 m (derate 1%/100 m above 1000 m, up to 4000 m)
Relative Humidity 5%-95% (non-condensing)

Control & Functional Parameters

Parameter Specification
Control Principle Direct Torque Control (DTC, standard); scalar control (optional)
Speed Control Range 1:1000 (with encoder feedback); 1:100 (open-loop, V/f control)
Current Control Accuracy ±0.5% of rated current (closed-loop, steady state)
Speed Control Accuracy ±0.01% of nominal speed (with encoder, steady state)
Frequency Resolution 0.01 Hz (digital reference); 0.001 Hz (analog reference)
Acceleration/Deceleration Time 0.1-3600 s (adjustable, parameters P1120/P1121)
I/O Interface Standard: 6 digital inputs, 4 digital outputs, 2 analog inputs (0-10 V/4-20 mA), 2 analog outputs (0-10 V/4-20 mA); expandable via I/O extension modules
Fieldbus Support Modbus RTU (built-in); PROFIBUS DP, Ethernet/IP (optional via communication modules)
Operator Panel ACS-AP-I Industrial Assistant control panel (J425, default); supports ABB Control Panel (ACP, optional)
Safety Functions Safe Torque Off (STO, SIL 3, standard); Safe Stop 1 (SS1, optional)

Environmental & Safety Parameters

Parameter Specification
Line Imbalance Tolerance Max ±3% of nominal phase-to-phase input voltage
Short-Circuit Withstand Capacity 100 kA (symmetrical, 1 s, 400 V AC input)
EMC Compliance EN 61800-3 (C2 category, standard); C3 category (optional with EMC filter)
Certifications CE, UL, CSA, IEC 61800-5-1
Vibration Resistance 5-15 Hz: 0.1 g; 15-150 Hz: 0.5 g (IEC 60068-2-6)
Shock Resistance 10 g (11 ms, half-sine, IEC 60068-2-27)