ACS880-01-293A-3+J425+R700 English Technical Parameters (Detailed)
This is a 3-phase wall-mounted industrial AC drive from ABB’s ACS880-01 series, with a rated output power of 160 kW (400 V, 3-phase), a rated output current of 293 A (Normal Duty), equipped with ACS-AP-I Industrial Assistant control panel (J425) and English documentation (R700)ABB Group. The detailed English parameters are as follows:
Core Electrical Parameters
| Parameter | Specification |
|---|---|
| Model | ACS880-01-293A-3+J425+R700 |
| Product Type | LV AC Industrial Wall-Mounted Single Drive (IEC Standard) |
| Input Voltage (Uin) | 3-phase, 380-480 V AC (±10%), 50/60 Hz (47.5-63 Hz allowed) |
| Input Frequency | 47.5-63 Hz |
| Output Voltage (Uout) | 0-Uin (3-phase, 380-480 V AC) |
| Output Frequency Range | 0-500 Hz |
| Output Current (Normal Duty, In) | 293 A |
| Output Current (Heavy Duty, IHD) | 246 A |
| Output Current (Light Overload, ILD) | 278 A |
| Output Power (Normal Duty, Pn) | 160 kW (at 400 V) |
| Output Power (Heavy Duty, PHD) | 132 kW |
| Output Power (Light Overload, PLD) | 160 kW |
| Number of Phases (Input/Output) | 3-phase |
| Overload Capacity | 1.5 × In for 1 min (293 A × 1.5 = 439.5 A, max. 1 min every 5 min); 1.1 × In for continuous operation |
| Switching Frequency | 2-16 kHz (adjustable, default 4 kHz) |
| Efficiency (at Nominal Power) | 98% (approx.) |
| Power Factor (Fundamental) | 0.98 |
| Power Factor (Total) | 0.95 (approx., at full load) |
| Input Reactor | Standard (built-in) |
| Brake Chopper | Standard (for frame size R8) |
Option Code Definitions (J425+R700)
| Option Code | Function Description |
|---|---|
| J425 | ACS-AP-I Industrial Assistant control panel (compatible with ACS380, 580, 880; supports parameter setting, monitoring, diagnostics, and maintenance guidance) |
| R700 | Documentation/manuals in English (printed copy and electronic version for quick commissioning and maintenance) |
Physical & Installation Parameters
| Parameter | Specification |
|---|---|
| Frame Size | R8 |
| Mounting Type | Wall-mounted (standard); cabinet-assembly (optional) |
| Protection Class | IP21 (standard, wall-mounted); IP55 (optional, for dusty/wet environments) |
| Enclosure Type NEMA | Type 1 |
| Dimensions (H×W×D) | 965 mm × 300 mm × 386 mm |
| Net Weight | 68 kg |
| Cooling Method | Forced air cooling (internal fan, 230 V AC fan supply) |
| Ambient Temperature (Operating) | -10°C to +40°C (derate 1%/°C above 40°C, up to 50°C) |
| Ambient Temperature (Storage) | -40°C to +70°C |
| Altitude | ≤1000 m (derate 1%/100 m above 1000 m, up to 4000 m) |
| Relative Humidity | 5%-95% (non-condensing) |
Control & Functional Parameters
| Parameter | Specification |
|---|---|
| Control Principle | Direct Torque Control (DTC, standard); scalar control (optional) |
| Speed Control Range | 1:1000 (with encoder feedback); 1:100 (open-loop, V/f control) |
| Current Control Accuracy | ±0.5% of rated current (closed-loop, steady state) |
| Speed Control Accuracy | ±0.01% of nominal speed (with encoder, steady state) |
| Frequency Resolution | 0.01 Hz (digital reference); 0.001 Hz (analog reference) |
| Acceleration/Deceleration Time | 0.1-3600 s (adjustable, parameters P1120/P1121) |
| I/O Interface | Standard: 6 digital inputs, 4 digital outputs, 2 analog inputs (0-10 V/4-20 mA), 2 analog outputs (0-10 V/4-20 mA); expandable via I/O extension modules |
| Fieldbus Support | Modbus RTU (built-in); PROFIBUS DP, Ethernet/IP (optional via communication modules) |
| Operator Panel | ACS-AP-I Industrial Assistant control panel (J425, default); supports ABB Control Panel (ACP, optional) |
| Safety Functions | Safe Torque Off (STO, SIL 3, standard); Safe Stop 1 (SS1, optional) |
Environmental & Safety Parameters
| Parameter | Specification |
|---|---|
| Line Imbalance Tolerance | Max ±3% of nominal phase-to-phase input voltage |
| Short-Circuit Withstand Capacity | 100 kA (symmetrical, 1 s, 400 V AC input) |
| EMC Compliance | EN 61800-3 (C2 category, standard); C3 category (optional with EMC filter) |
| Certifications | CE, UL, CSA, IEC 61800-5-1 |
| Vibration Resistance | 5-15 Hz: 0.1 g; 15-150 Hz: 0.5 g (IEC 60068-2-6) |
| Shock Resistance | 10 g (11 ms, half-sine, IEC 60068-2-27) |