Core Technical Specifications
| Parameter | Value |
|---|---|
| Model | ACS880-104-0050A-5 |
| Product ID | 3AUA0000140071 |
| Voltage & Frequency | Input (DC Bus): 510-900 VDC; Output: 3-phase, 0-415 VAC, 0-500 Hz |
| Current Ratings | Normal (Iₙ): 50 A; Light Overload (Iₗd): 47.5 A; Heavy Duty (Iₕd): 41.7 A; Max Output Current: 75 A (415 VAC, 10s) |
| Power Ratings | Normal (Pₙ): 25 kW (33.5 HP); Light Overload (Pₗd): 25 kW (33.5 HP); Heavy Duty (Pₕd): 20 kW (26.8 HP) |
| Apparent Power | 34 kVA |
| Efficiency | IE2; Standby loss: 65 W; Operating efficiency up to 98.0% |
| Power Dissipation | 480 W |
| Enclosure | IP00 (for cabinet integration); Frame Size R2 |
| Dimensions (W×H×D) | 260 mm × 380 mm × 220 mm (10.24 in × 14.96 in × 8.66 in) |
| Net Weight | 12 kg (26.46 lb) |
| Ambient Conditions | Operating Temperature: -15 to +40 °C; Storage Temperature: -40 to +70 °C; Humidity: 5-95% RH (non – condensing); Altitude: up to 4000 m |
| Safety Features | Safe Torque Off (STO, SIL 3/PL e), Emergency Stop, Direct Torque Control (DTC)ABB Group |
| I/O Interfaces | Digital: 6 inputs, 2 relay outputs (2 A/250 VAC); Analog: 2 inputs (0-10 V/4-20 mA), 2 outputs (0-20 mA); Communication: RS – 485 (Modbus RTU), USB, optional fieldbus adapters |
| Standard Features | Built – in DC link capacitor, DTC motor control for induction, PM, and synchronous reluctance motors; STO as standardABB Group |