Core Technical Specifications
| Parameter | Value |
|---|---|
| Model | ACS880-104-0240A-5 |
| Product ID | 3AUA0000140127 |
| Voltage & Frequency | Input (DC Bus): 510-900 VDC; Output: 3-phase, 0-415 VAC, 0-500 Hz |
| Current Ratings | Normal (Iₙ): 240 A; Light Overload (Iₗd): 228 A; Heavy Duty (Iₕd): 192 A; Max Output Current: 360 A (415 VAC, 10s) |
| Power Ratings | Normal (Pₙ): 110 kW (150 HP); Light Overload (Pₗd): 110 kW (150 HP); Heavy Duty (Pₕd): 90 kW (120 HP) |
| Apparent Power | 150 kVA |
| Efficiency | IE2; Standby loss: 280 W; Operating efficiency up to 98.5% |
| Power Dissipation | 2100 W |
| Enclosure | IP00 (open module for cabinet integration); Frame Size R6 |
| Dimensions (W×H×D) | 440 mm × 700 mm × 340 mm (17.32 in × 27.56 in × 13.39 in) |
| Net Weight | 48 kg (105.82 lb) |
| Ambient Conditions | Operating Temp: -15 to +40 °C; Storage Temp: -40 to +70 °C; Humidity: 5-95% RH (non – condensing); Altitude: up to 4000 m |
| Safety Features | Safe Torque Off (STO, SIL 3/PL e), Emergency Stop, Direct Torque Control (DTC) |
| I/O Interfaces | Digital: 6 inputs, 2 relay outputs (2 A/250 VAC); Analog: 2 inputs (0-10 V/4-20 mA), 2 outputs (0-20 mA); Communication: RS – 485 (Modbus RTU), USB, optional fieldbus adapters |
| Standard Features | Built – in DC link capacitor, DTC for induction, PM, synchronous reluctance motors; STO as standardABB Group |