This datasheet specifies the ABB ACS880-01-0032A-3+N5050, a wall-mounted, IP21-protected 3-phase AC drive with 32A output current and 22kW (30HP) rating at 400V, integrated with Direct Torque Control (DTC) and the N5050 functional safety option for enhanced operational protection in industrial applicationsABB Group.
General Information
| Item | Specification |
|---|---|
| Model Number | ACS880-01-0032A-3+N5050 |
| Product Family | ACS880 Series |
| Ordering Code | 3AXD50000046387 (base) + N5050 |
| Frame Size | R4 |
| Mounting Type | Wall-mounted |
| Enclosure Protection | IP21 (UL Type 1) |
| Control Panel | Assistant Bluetooth |
| Main Option | N5050 (Functional Safety Option) |
Electrical Ratings
| Parameter | Value |
|---|---|
| Input Voltage | 3-phase, 380-480V AC (400V nominal), 50/60Hz |
| Output Voltage | 3-phase, 0-Input Voltage, 0-500Hz (varies with control mode) |
| Output Current (Normal Duty) | 32A (22kW/30HP) |
| Output Current (Heavy Duty) | 27A (18.5kW/25HP) |
| Rated Power | 22kW (30HP normal duty), 18.5kW (25HP heavy duty) |
| Overload Capacity | 110% for 1 minute, 150% for 3 seconds (typical) |
| Efficiency | >98% (at rated load) |
| Power Factor | >0.98 (at rated load) |
Mechanical Dimensions & Weight
| Dimension | Value |
|---|---|
| Height | 26.8 in (680 mm) |
| Width | 8.3 in (210 mm) |
| Depth | 10.3 in (262 mm) |
| Net Weight | 44.1 lbs (20 kg) |
Communication & Control
| Feature | Specification |
|---|---|
| Control Method | Direct Torque Control (DTC) |
| Standard Protocols | Modbus RTU, PROFIBUS DP, Ethernet/IP (optional) |
| I/O Configuration | 6 digital inputs, 2 relay outputs, 2 analog inputs, 1 analog output (configurable) |
Protection & Safety (Including N5050 Option)
| Protection Feature | Description |
|---|---|
| Overcurrent Protection | Trips when output current exceeds the set limit |
| Overvoltage Protection | Activates when DC bus voltage is too high |
| Undervoltage Protection | Triggers when input voltage is below the minimum threshold |
| Overtemperature Protection | Shuts down the drive if heatsink temperature is excessive |
| Short Circuit Protection | Guards against output short circuits |
| Integrated Safety (N5050) | Adds STO (Safe Torque Off) and other functional safety functions for higher-level safety compliance |
Environmental Conditions
| Condition | Range |
|---|---|
| Operating Temperature | -10°C to +40°C (14°F to 104°F); derate 1% per 10°C above 40°C |
| Storage Temperature | -40°C to +70°C (-40°F to 158°F) |
| Relative Humidity | 5% to 95% (non-condensing) |
| Altitude | Up to 1000m (3300ft) without derating; derate 1% per 100m above 1000m |
| Vibration | 0.5g (5Hz to 150Hz) |