This datasheet specifies the Siemens SINAMICS S120 Active Interface Module 6SL3300-7TE41-4AA0, designed for high-power industrial drive systems with Active Line Modules (ALM) 6SL3330-7TE41-0AA3/41-2AA3/41-4AA3 (630–900 kW). It has been replaced by 6SL3300-7TE41-4AA1.
Core Product & Ordering Info
| Item | Detail |
|---|---|
| Part Number | 6SL3300-7TE41-4AA0 |
| Replaced By | 6SL3300-7TE41-4AA1 |
| Product Type | Active Interface Module (AIM), SINAMICS S120 Chassis Format |
| Compatible ALM | 6SL3330-7TE41-0AA3 (630 kW), 6SL3330-7TE41-2AA3 (800 kW), 6SL3330-7TE41-4AA3 (900 kW) |
| Main Function | Clean Power Filter (basic RI suppression), pre-charging circuit, line voltage sensing, monitoring sensors |
| Cooling | Internal air-cooled (chassis format) |
| Net Weight | 551 kg |
Electrical Specifications
| Parameter | Value |
|---|---|
| Line Voltage (3AC) | 380–480 V (rated 400 V class) |
| Frequency | 50/60 Hz (47–63 Hz tolerance) |
| Rated Current (ALM 900 kW) | 1405 A (continuous) |
| Rated Current (ALM 630 kW) | 985 A (continuous) |
| DC Link Voltage | 510–720 V DC (matches ALM output) |
| Power Rating | 630–900 kW (matches ALM rating) |
| EMC Compliance | Clean Power Filter for basic RI suppression; meets EN 61800-3 |
| Control Voltage | 24 V DC (auxiliary power for control circuits) |
Mechanical & Environmental
| Parameter | Value |
|---|---|
| Frame Size | JI (chassis format) |
| IP Rating | IP00 (built-in unit, no external protection) |
| Operating Temperature | 0–40 °C (no derating up to 40 °C) |
| Storage Temperature | -25–70 °C |
| Relative Humidity | ≤80% (non-condensing, 0–40 °C) |
| Altitude | ≤1000 m (derate 1% per 100 m above 1000 m, max 4000 m) |
| Vibration/Shock | Compliant with IEC 60068-2-6/2-27 |
Interfaces & Key Components
| Interface/Component | Configuration |
|---|---|
| DRIVE-CLiQ | Integrated port for ALM and Control Unit (CU) connection; includes DRIVE-CLiQ cable with Pt1000 |
| Line Connection | 3× M12 sockets (line/load terminals) |
| Monitoring | Voltage/current sensing, temperature monitoring (Pt1000), pre-charge status |
| Protections | Overcurrent, overvoltage, undervoltage, overtemperature, short-circuit, EMC filtering |
| Contactor | Bypass contactor (integral for JI frame) |
Key Features
- Clean Power Filter: Reduces line harmonics and RF interference (basic RI suppression) for industrial grids.
- Pre-Charging Circuit: Safely charges the DC link capacitor bank during startup, preventing inrush current damage.
- Seamless Integration: Works with SINAMICS S120 CU320-2/CU310-2 for centralized control and diagnostics.
- High Reliability: Coated PCBs, heavy-duty busbars, and factory testing for harsh industrial use.
- Safety Compliance: Meets EN 61800-5-1 (functional safety) and IEC 61800-3 (EMC).