- Product Family: SINAMICS G120 Power Module PM240-2
- Order No.: 6SL3210-1PE31-1UL0
- Key Features: No integrated line filter; built-in braking chopper; requires separate control unit (e.g., CU250S-2)
- Input: 3-phase AC 380–480 V ±10%/-20%, 47–63 Hz
- Output: 3-phase AC (variable frequency/voltage), max output frequency up to 550 Hz
- Rated Power:
- High Overload (HO): 45 kW (200% for 3 s, 150% for 57 s, 100% continuous; cycle 300 s)
- Low Overload (LO): 55 kW (150% for 3 s, 110% for 57 s, 100% continuous; cycle 300 s)
- Protection: IP20 (without control unit/BOP), UL open type
- Cooling: Forced air cooling (integrated fan)
- Frame Size: FSE
- Certifications: CE, UL, CUL, RCM (C-Tick), RoHS compliant, EN 50598-2 (IE2 efficiency class)
Key Technical Specifications (English)
| Parameter | Value |
|---|---|
| Rated Output Current (HO) | 90 A |
| Rated Output Current (LO) | 110 A |
| Max Overload Current | 180 A (200% HO, 3 s) |
| Pulse Frequency | 2–8 kHz (adjustable, default 4 kHz) |
| Control Modes (with CU) | V/f, vector control (SLVC), servo control |
| Ambient Temperature (HO/LO) | -20…+50 °C (HO); -20…+40 °C (LO) |
| Installation Altitude | Up to 1000 m (derating above 1000 m) |
| Dimensions (H×W×D) | 551 × 275 × 237 mm |
| Net Weight | 26.0 kg |
| Power Loss (rated) | ~1.54 kW |
| Efficiency (rated) | ~98% |
| Sound Pressure Level (1 m) | 71 dB |
| Motor Cable Length (shielded/unshielded) | Up to 100 m (shielded), 50 m (unshielded) |
| Braking Chopper | Integrated (external braking resistor required) |
Download & Usage Notes
- Set language to English (top-right corner) on Siemens official pages to access English docs.
- Download the full PDF datasheet for complete details: derating curves, wiring diagrams, EMC guidelines, safety instructions, CAD data, and firmware compatibility (CU V4.7 HF8+ recommended).
- Cross-check with the SINAMICS G120 PM240-2 Operating Instructions for system integration, commissioning, and fault troubleshooting.
- Always verify the latest revision date for project compliance and technical accuracy.