- Order No.:6SL3210-1SE31-0AA0
- Product Family:SINAMICS S120 PM340 Power Module (Blocksize frame FSE, built-in line filter)
- Core Function:3-phase inverter power module for motor drive; internal air cooling; integrated line filter for EMC compliance; DRIVE-CLiQ communication; non-regenerative (braking energy via external resistor)
- Input:3AC 380–480 V, 50/60 Hz
- Output:3AC, 90 A rated current, 45 kW rated power (at 400 V AC input)
- Cooling:Internal air cooling (integral fan)
- Enclosure:IP20 (open blocksize, rack-mountable)
- Certifications:CE, UL, CUL, RoHS compliant
- Country of Origin:Germany
- Net Weight:~20 kg (44.09 lbs) (refer to full datasheet for exact value)
- Lifecycle Status:Phase-out (discontinued since 01.10.2019; spare part only)
Key Technical Specifications (English)
| Parameter | Value |
|---|---|
| Rated Input Voltage | 3AC 380–480 V, 50/60 Hz |
| Rated Input Current | 94/105 A (nominal/max) |
| Rated Output Current | 90 A (3AC) |
| Rated Output Power | 45 kW (at 400 V AC input) |
| DC Link Voltage | 510–650 V DC (nominal 600 V DC) |
| Auxiliary Power Supply | 24 V DC (-15% / +20%) |
| Frame Size | Blocksize FSE |
| Cooling Type | Internal air cooling (built-in fan) |
| Operating Temperature | 0 … +40 °C (no derating up to 1000 m); derate linearly above 40 °C |
| Storage Temperature | -25 … +70 °C |
| Relative Humidity | 5 … 95% (non-condensing) |
| Installation Altitude | Up to 2000 m (derating above 1000 m) |
| Communication | DRIVE-CLiQ (integrated, for control unit connection) |
| Safety Features | Overvoltage/overcurrent/overtemperature protection; STO (Safe Torque Off) support via control unit/motor module |
| Compliance | EN 61800‑3, IEC 60947-6-2, UL 508C, CSA C22.2 No. 14 |
| EMC | Integrated line filter; meets industrial EMC standards |
| Dimensions (H×W×D) | ~633 × 275 × 203.5 mm (refer to full datasheet for exact) |
Download & Usage Notes
- Set language to English (top-right corner) on Siemens Industry Mall to access English-only documents.
- Download the full PDF datasheet for complete details: exact dimensions, derating curves, EMC guidelines, wiring diagrams, M-CAD/E-CAD (STEP/DXF), firmware compatibility, and safety instructions.
- Pair with SINAMICS S120 Control Unit (e.g., CU320-2 series) and Basic/Active Line Module (e.g., 6SL3130/6SL3330 series) for complete drive system; use external braking resistor for energy dissipation (no regeneration to grid).
- Verify the latest revision date for project compliance and technical accuracy; check SIOS for successor product (PM410 series) for new designs.
- Use STARTER or TIA Portal software for configuration, commissioning, and diagnostics.