Product Identification
Product Name: SINAMICS S120 Basic Line Module, Chassis Type
Order Number: 6SL3330-1TE41-2AA3
Product Status: Active (PM300)
Cooling: Internal air cooling
Protection: IP00, built-in unit with CIM (Control Interface Module)
Included: Drive-CLiQ cable
Core Electrical Parameters (Voltage, Current, Power, Full Ratings)
| Parameter | Value |
|---|---|
| Input supply | 3-phase AC, 380 V … 480 V AC |
| Input frequency | 50/60 Hz, permissible 47 … 63 Hz |
| Rated input voltage | 400 V AC (50 Hz) / 460 V AC (60 Hz) |
| Rated input current (In_E) | 1010 A |
| Max input current (Imax_E) | 1515 A |
| Max precharge current (≤3 s) | Internal limited |
| DC-link output voltage | 510 V … 650 V DC; nominal ~1.35 × line voltage |
| Rated DC current (In_DC) | 1200 A |
| Base load DC current (IH_DC, 50 Hz) | 860 A |
| Base load DC current (IH_DC, 60 Hz) | 690 A |
| Max DC current (Imax_DC) | 1800 A |
| Type rating / Rated power | 560 kW |
| Equivalent horsepower | 750 HP |
| Auxiliary electronics supply | 24 V DC (range 20.4 … 28.8 V DC) |
| Electronics current consumption (24 V DC) | 1.1 A |
| Fan supply voltage | 230 V AC (195.5 … 264.5 V AC) |
| Fan power consumption | 4.5 A |
| Total typical power loss | 4.6 kW |
Mechanical & Environmental Specifications
- Net weight: 320 kg
- Operating temperature (no derating): 0 … +40 °C
- Operating temperature (with derating): up to +55 °C
- Storage temperature: -20 … +60 °C
- Relative humidity: 5 … 95%, non-condensing
- Cooling air flow requirement: 0.36 m³/s
- Acoustic noise (1 m, 50/60 Hz): 71 / 73 dB(A)
- Terminals: Line & DC-link with M12 connectors
- Max cable cross-section:
- Line input (U1/V1/W1): 6×185 mm²
- DC-link (DCP/DCN): 4×240 mm²
- Max total cable length (shielded): 4000 m; (unshielded): 6000 m
- DC-link capacitance (internal): 23200 µF; system max up to 185600 µF
Interface & Functional Features
- Communication: DRIVE-CLiQ interface (standard cable included)
- Control interface: Integrated CIM for parameterization, diagnostics, safety
- Safety functions: Extended Safety Integrated functions supported
- Topology: Basic rectifier, non-regenerative, for DC-link supply of S120 drives
- EMC compliance: EN 55011 Class A, EN 61000-6-2 / EN 61000-6-4
- Certifications: CE, cULus, RCM, KC, RoHS compliant
- Recommended line reactor: 6SL3000-0CE41-0AA0 (for harmonic mitigation & voltage stabilization)