Soft starter, Altistart 480, 250A, 208 to 690V AC, control supply 110 to 230V AC
ATS480C25Y
| Range of Product | Altivar Soft Starter ATS480 |
| Product or Component Type | Soft starter |
| product destination | Asynchronous motors |
| Product Specific Application | Process and infrastructures |
| Device short name | ATS480 |
| Phase | 3 phase |
| Utilisation category | AC-3A |
| AC-53A | |
| Ue power supply voltage | 208…690 V – 15…10 % |
| power supply frequency | 50…60 Hz – 20…20 % |
| [Ie] rated operational current | Normal duty 250.0 A 104 °F (40 °C)) |
| rated current in heavy duty | 210.0 A at 104 °F (40 °C) heavy duty |
| Torque control | TRUE |
| IP Degree of Protection | IP00 |
| Motor power kW | 75.0 kW 230 V in the motor supply line normal duty |
| 55.0 kW 230 V in the motor supply line heavy duty | |
| 132.0 kW 400 V in the motor supply line normal duty | |
| 110.0 kW 400 V in the motor supply line heavy duty | |
| 132.0 kW 440 V in the motor supply line normal duty | |
| 110.0 kW 440 V in the motor supply line heavy duty | |
| 160.0 kW 500 V in the motor supply line normal duty | |
| 132.0 kW 500 V in the motor supply line heavy duty | |
| 160.0 kW 525 V in the motor supply line normal duty | |
| 132.0 kW 525 V in the motor supply line heavy duty | |
| 220.0 kW 660 V in the motor supply line normal duty | |
| 160.0 kW 660 V in the motor supply line heavy duty | |
| 250.0 kW 690 V in the motor supply line normal duty | |
| 200.0 kW 690 V in the motor supply line heavy duty | |
| 132.0 kW 230 V to the motor delta terminals normal duty | |
| 110.0 kW 230 V to the motor delta terminals heavy duty | |
| 220.0 kW 400 V to the motor delta terminals normal duty | |
| 160.0 kW 400 V to the motor delta terminals heavy duty | |
| Maximum Horse Power Rating | 75.0 hp 208 V normal duty |
| 60.0 hp 208 V heavy duty | |
| 100.0 hp 230 V normal duty | |
| 75.0 hp 230 V heavy duty | |
| 200.0 hp 460 V normal duty | |
| 150.0 hp 460 V heavy duty | |
| 250.0 hp 575 V normal duty | |
| 200.0 hp 575 V heavy duty | |
| Option card | Communication module Profibus DP V1 |
| Communication module PROFINET | |
| Communication module Modbus TCP/EtherNet/IP | |
| Communication module CANopen daisy chain | |
| Communication module CANopen Sub-D | |
| Communication module CANopen open style |
| Device connection | In the motor supply line |
| To the motor delta terminals | |
| [Us] control circuit voltage | 110…250 V AC 50/60 Hz – 15…10 % |
| Apparent power | 0.106 kVA |
| Integrated motor overload protection | TRUE |
| motor thermal protection class | Class 10E |
| Protection type | Phase failure line |
| Integrated thermal protection motor | |
| Thermal protection starter | |
| Current overload motor | |
| Underload motor | |
| Excessive starting time, locked rotor motor | |
| Motor phase loss motor | |
| Line supply phase loss line | |
| Line supply phase loss motor | |
| Thermal protection motor | |
| current limiting %In (5 x Ie maximum) | 150…700 % |
| [In] Rated current pwr loss specifctn | 250.0 A |
| Power loss static current independent | 25.0 W |
| Power loss per device current dependent | 675.0 W |
| Standards | IEC 60947-4-2 |
| UL 60947-4-2 | |
| IEC 60664-1 | |
| Product Certifications | CE |
| cULus | |
| CCC | |
| UKCA | |
| RCM | |
| EAC | |
| DNV | |
| ABS | |
| BV | |
| CCS | |
| marking | CE |
| CCC | |
| UKCA | |
| EAC | |
| RCM | |
| CULus | |
| [Uc] control circuit voltage | 24 V DC |
| Discrete input number | 4 |
| Discrete input type | STOP) logic inputs, 3500 Ohm |
| RUN) logic inputs, 3500 Ohm | |
| DI3) programmable as logic input, 3500 Ohm | |
| DI4) programmable as logic input, 3500 Ohm | |
| Input compatibility | STOP discrete input level 1 PLC IEC 61131-2 |
| RUN discrete input level 1 PLC IEC 61131-2 | |
| DI3 discrete input level 1 PLC IEC 61131-2 | |
| DI4 discrete input level 1 PLC IEC 61131-2 | |
| Discrete input logic | Programmable digital input < 5 V |
| Relay output number | 3 |
| Relay output type | Relay outputs R1A 1 NO |
| Relay outputs R1B 1 NO | |
| Relay outputs RIC NO/NC programmable | |
| Minimum switching current | 100 mA 12 V DC relay outputs |
| Maximum switching current | Relay outputs 2 A 250 V AC |
| Relay outputs 2 A 30 V DC | |
| Relay outputs | |
| Discrete output number | 2 |
| Discrete output type | DQ1) programmable digital output <= 30 V |
| DQ2) programmable digital output <= 30 V | |
| Output compatibility | Open collector level 1 PLC IEC 65A-68 |
| analogue input number | 1 |
| Analogue input type | AI1/PTC PTC/Pt 100 temperature probe |
| PTC2 PTC/Pt 100 temperature probe | |
| PTC3 PTC/Pt 100 temperature probe | |
| analogue output number | 1 |
| Analogue output type | Current output AQ1 0…20 mA or 0…10 V 500 Ohm |
| Communication Port Protocol | Modbus serial |
| Connector Type | 1 RJ45 |
| Communication data link | Serial |
| Physical interface | 2-wire RS 485 |
| Transmission Rate | 1200…256000 bit/s |
| Transmission frame | RTU |
| Data format | 8 bits, configurable odd, even or no parity |
| Type of polarization | No impedance Modbus serial |
| Number of addresses | 0…227 Modbus serial |
| Method of access | Slave Modbus serial |
| Function Available | External bypass control |
| Pre-heating | |
| Smoke extraction | |
| Multi-motor cascade | |
| Second motor set | |
| User management | |
| Ports and services hardening | |
| Security event logging | |
| Cybersecure firmware update | |
| Single direction | |
| Display screen available | TRUE |
| Operating position | Vertical +/- 10 degree |
| Height | 14.96 in (380.0 mm) |
| Width | 12.60 in (320.0 mm) |
| Depth | 10.91 in (277.0 mm) |
| Net Weight | 40.12 lb(US) (18.2 kg) |
| Electromagnetic compatibility | Conducted and radiated emissions level A IEC 60947-4-2 |
| Conducted and radiated emissions with bypass level B IEC 60947-4-2 | |
| Damped oscillating waves level 3 IEC 61000-4-12 | |
| Electrostatic discharge level 3 IEC 61000-4-11 | |
| Immunity to electrical transients level 4 IEC 61000-4-4 | |
| Immunity to radiated radio-electrical interference level 3 IEC 61000-4-3 | |
| Voltage/current impulse level 3 IEC 61000-4-5 | |
| Pollution degree | Level 3 |
| [Uimp] rated impulse withstand voltage | 6 kV |
| [Ui] Rated Insulation Voltage | 690 V |
| Environmental class (during operation) | Class 3C3 according to IEC 60721-3-3 |
| Class 3S2 according to IEC 60721-3-3 | |
| Relative humidity | 0…95 % without condensation or dripping water IEC 60068-2-3 |
| Ambient air temperature for operation | 104…140 °F (40…60 °C) with current derating of 2 % per °C) |
| 5…104 °F (-15…40 °C) without derating) | |
| Ambient Air Temperature for Storage | -13…158 °F (-25…70 °C) |
| Operating altitude | <= 3280.84 ft (1000 m) without derating |
| > 3280.84…13123.36 ft (> 1000…4000 m) with current derating 1 % per 100 m | |
| Maximum deflection under vibratory load (during operation) | 1.5 mm at 2…13 Hz |
| Maximum deflection under vibratory load (during storage) | 1.75 mm at 2…9 Hz |
| Maximum deflection under vibratory load (during transport) | 1.75 mm at 2…9 Hz |
| Maximum acceleration under vibrational stress (during operation) | 10 m/s² at 13…200 Hz |
| Maximum acceleration under vibratory load (during storage) | 15 m/s² at 200…500 Hz |
| 10 m/s² at 9…200 Hz | |
| Maximum acceleration under vibratory load (during transport) | 15 m/s² at 200…500 Hz |
| 10 m/s² at 9…200 Hz | |
| Maximum acceleration under shock impact (during operation) | 150 m/s² at 11 ms |
| Maximum acceleration under shock load (during storage) | 100 m/s² at 11 ms |
| Maximum acceleration under shock load (during transport) | 100 m/s² at 11 ms |