This is a detailed English parameter sheet for the ABB ACS800‑04‑2120‑7 (single‑drive module) with options E205, V991, covering core electrical ratings, option specs, communication, physical‑environmental data, and compliance for industrial motor control applicationsABB Group.
Core Electrical Ratings
| Parameter | Value | Notes |
|---|---|---|
| Input Voltage (U₁) | 3AC 525–690 V (50/60 Hz) | 7th voltage code; tolerance ±10% |
| Rated Input Current (I₁ₙ) | 2120 A (rms, 3‑phase) | At 690 V rated voltage |
| Rated Output Power (Pₒᵤₜₙ) | 1200 kW (at 690 V, 50 Hz) | DTC control; 98% nominal efficiency |
| Rated Output Current (Iₒᵤₜₙ) | 2120 A (rms, 3‑phase) | Continuous at 40°C ambient |
| Output Voltage (Uₒᵤₜ) | 0–690 V (3‑phase, variable) | Matches input voltage range |
| Output Frequency (fₒᵤₜ) | 0–300 Hz (standard); ±300 Hz (optional) | Speed/torque control range |
| DC Link Voltage (U<sub>DC</sub>) | ~1000 VDC (unloaded); ~950 VDC (loaded) | Diode rectifier output |
| Overload Capacity | 110% Iₙ for 60 s; 150% Iₙ for 1 s | Per ABB single‑drive design specs |
| Power Loss (P<sub>loss</sub>) | ~10.5 kW (typical, at rated load) | Includes module + option power draw |
| Auxiliary Supply (Uₐᵤₓ) | 24 VDC (19.2–28.8 VDC) | Control circuit power |
| Auxiliary Current (Iₐᵤₓ) | 5 A (max) | For logic, I/O, and cooling fans |
Option Specifications (E205+V991)
| Option | Type | Key Parameters | Function |
|---|---|---|---|
| E205 | Integrated EMC Filter | EN 61800‑3 C2 compliance; 150 kHz–30 MHz attenuation | Reduces conducted/radiated emissions |
| V991 | Advanced Protection SW | Overvoltage/overcurrent/ground‑fault monitoring; thermal modeling | Enhanced drive/motor protection |
Communication & Control
| Parameter | Value | Details |
|---|---|---|
| Control Method | Direct Torque Control (DTC) | Speed/torque control without encoder |
| Digital Inputs | 6 (programmable, 24 VDC) | 24 VDC, -15% to +20% tolerance |
| Analog Inputs | 3 (0/4–20 mA or 0/2–10 V) | 12‑bit resolution; galvanically isolated |
| Analog Outputs | 2 (0/4–20 mA) | Max load impedance ≤700 Ω |
| Relay Outputs | 3 (programmable) | 8 A at 24 VDC/250 VAC; 0.4 A at 120 VDC |
| Fieldbus Options | Profibus DP, Modbus RTU, CANopen | V991 enables remote diagnostics |
Physical & Environmental
| Parameter | Value | Limits |
|---|---|---|
| Dimensions (H×W×D) | 2000 × 600 × 300 mm | Cabinet‑mounted profile |
| Weight | 320 kg | Steel housing; IP20 rear protection |
| Protection Class | Front: IP00; Rear: IP20 | Cabinet‑mount only (indoor use) |
| Ambient Temp (Operation) | 0–40°C | Derate 1%/°C above 40°C (max 50°C) |
| Ambient Temp (Storage) | -40–70°C | No condensation |
| Relative Humidity | 5–95% (non‑condensing) | Operation/storage |
| Altitude | ≤ 1000 m | Derate 1%/100 m above 1000 m |
| Vibration/Shock | IEC 60068‑2‑6 (vibration); IEC 60068‑2‑27 (shock) | 10–500 Hz, 0.5 g (vibration); 15 g (shock, 11 ms) |
Protection & Compliance
| Feature | Details | |
|---|---|---|
| Overvoltage | Clamping at 1.3×U<sub>DC</sub> | Transient surge protection |
| Overcurrent | Electronic current limiting | Trips at >150% Iₙ (sustained) |
| Short‑Circuit | Fuse‑protected input (optional) | 200 kA SCCR (690 V) |
| Standards | CE, UL 508C, cUL, IEC 61800‑5‑1 | Industrial safety/EMC compliance |