The ACS880-01-105A-3+D150+N5050 is a 3-phase AC single-drive of ABB ACS880 series, frame size R6 with IP21 enclosure for wall – mounted installation. +D150 is an integrated brake chopper for efficient motor braking, and +N5050 is a crane control program for hoisting applications. Below is its detailed technical parameter sheet:
1. Core Electrical Parameters
| Parameter | Specification |
|---|---|
| Rated Input Voltage (3-phase) | 380-415 V AC (400 V nominal); Allowable voltage range: 380-500 V AC |
| Rated Input Frequency | 50/60 Hz (47.5-63 Hz allowable) |
| Rated Output Current (In, 40 °C ambient) | 105 A (continuous operation, 3-phase)ABB Group |
| Output Current (Light Overload, ILD) | 100 A (10% overload for 1 min per 5 min cycle)ABB Group |
| Output Current (Heavy Duty, IHD) | 87 A (50% overload for 1 min per 5 min cycle)ABB Group |
| Max Output Current (Imax) | 157.5 A (150% of rated current for 2 s); 115.5 A (110% of rated current for 60 s) |
| Rated Output Power (Pn, 400 V, cosφ=0.95) | 55 kWABB Group |
| Output Power (Light Overload, PLD) | 55 kWABB Group |
| Output Power (Heavy Duty, PHD) | 45 kWABB Group |
| Max Output Power | 60.5 kW (110% of rated power, 1 min per 10 min cycle) |
| Rated Output Voltage | 3-phase, 0 to max 480 V AC; Voltage regulation via PWM |
| Apparent Power Output | 73 kV·A (400 V AC, 105 A) |
| Power Factor (Output) | 0.95 (at rated load) |
| Power Loss (Rated Load) | 1850 W |
| Brake Chopper (D150 Option) | Rated braking power 55 kW; Max braking current 105 A; Braking duty cycle: 150% of rated current for 2 s |
2. Mechanical & Thermal Parameters
| Parameter | Specification |
|---|---|
| Cooling Method | Forced air cooling (standard) |
| Ambient Temperature | Operating: -10 °C to 40 °C (derate 1% / °C above 40 °C up to 50 °C); Storage: -40 °C to 70 °C |
| Enclosure Protection | IP21 (dust – protected, protected against dripping water) |
| Frame Size | R6ABB Group |
| Dimensions (H×W×D) | 726 mm × 251 mm × 357 mm (28.58 in × 9.88 in × 14.06 in) |
| Net Weight | 42.2 kg (93.04 lbs) |
| Noise Level | ≤ 68 dB(A) (1 m distance, rated load) |
| Altitude | Max 4000 m (derate 1% rated current per 100 m above 1000 m) |
| Operating Humidity | 5% – 95% (non – condensing) |
3. Control, I/O & Optional Features
| Parameter | Specification |
|---|---|
| Control Modes | DTC (Direct Torque Control), V/f control, sensorless vector control, vector control with encoder feedback |
| Digital Inputs | 6 × 24 V DC (configurable) |
| Digital Outputs | 2 × relay outputs (250 V AC / 30 V DC, 5 A) |
| Analog Inputs | 2 × (0-20 mA / 4-20 mA / 0-10 V) (configurable) |
| Analog Outputs | 2 × (0-20 mA / 4-20 mA) (configurable) |
| Communication Interfaces | Standard: Modbus RTU (RS – 485); Optional: PROFINET IO, EtherNet/IP, DeviceNet, PROFIBUS DP |
| Standby Loss | 42 W |
| D150 Brake Chopper Features | Integrated, no external chopper needed; Works with external brake resistors; Overvoltage/overcurrent protection |
| N5050 Crane Control Features | Hoisting logic, load monitoring, speed/torque control for cranes; Safe torque off (STO) integration |
4. Efficiency & Loss Data
| Parameter | Specification |
|---|---|
| Efficiency Level | IE2 |
| Absolute Loss (25% load) | 850 W; Efficiency: 96.5% |
| Absolute Loss (50% load) | 1100 W; Efficiency: 97.2% |
| Absolute Loss (100% load) | 1850 W; Efficiency: 97.5% |
5. Protection & Compliance
| Parameter | Specification |
|---|---|
| Protection Functions | Overvoltage, undervoltage, overcurrent, overload, overheating, short – circuit, earth fault, motor phase – loss protection; STO (SIL 3, PL e) as standard; Brake chopper overvoltage/overcurrent protection (D150 option) |
| Compliance Standards | IEC 61800-5-1, IEC 61800-3, CE, UL, CSA |
-150x150.png)