This datasheet follows ABB’s official ratings for the 400–500 V AC class, with clear distinctions between Heavy-Duty (HD/Constant Torque) and Light-Duty (LD/Variable Torque) operations, and precise thermal/mechanical data for cabinet integration.
1. Basic Identification & Core Power Ratings
| Parameter | Value | Notes |
|---|---|---|
| Order Number | ACS850-04-290A-5 | ABB Machinery Drive, single-axis module |
| Product Series | ACS850-04 | Cabinet-mountable open chassis |
| Frame Size | E0 | Defines cooling, dimensions, and accessories |
| Enclosure Protection | IP20 | Open type, for installation in customer cabinets |
| Nominal Output Current (Iₙ) | 290 A | Continuous 3-phase output at 40 °C |
| Rated Output Power (HD/CT) | 200 kW (268 HP) | Heavy-Duty / Constant Torque (S1) |
| Rated Output Power (LD/VT) | 160 kW (215 HP) | Light-Duty / Variable Torque (S1) |
| Input Voltage | 3-phase 380–500 V AC | +10% / –15%, 50/60 Hz |
| Output Voltage | 0–Input Voltage | 3-phase AC, sine-wave PWM |
| DC Link Voltage (Nominal) | 540–675 V DC | Derived from 400–500 V AC input |
| Overload Capacity | 110% × Iₙ for 1 min | 319 A; 150% × Iₙ for 2 s (peak) |
| Heat Dissipation (Typical) | 4200 W | At rated load, frame E0 |
2. Electrical Performance & Control Specifications
| Parameter | Value | |
|---|---|---|
| Control Method | Direct Torque Control (DTC); Scalar (V/f) optional | |
| Switching Frequency | 2–16 kHz, user-configurable (auto-tune available) | |
| Output Frequency Range | 0–599 Hz (0–500 Hz standard) | |
| Speed Control Accuracy | ±0.01% of rated speed (with encoder feedback) | |
| Torque Control Response | <5 ms (step rise time at nominal torque) | |
| Efficiency (η) | ≥97.2% | At rated load and 50 Hz |
| Input Power Factor | ≥0.96 | At rated load (with built-in mains choke) |
| EMC Compliance | EN 61800-3 (C3 for industrial environments); built-in EMC filter |
3. Environmental & Mechanical Data
| Parameter | Value | |
|---|---|---|
| Ambient Temperature (Operation) | 0–+40 °C (no derate); +40–+50 °C (10% derate) | |
| Ambient Temperature (Storage) | -40–+70 °C | |
| Altitude | ≤1000 m (no derate); 1000–3000 m (1% derate per 100 m) | |
| Humidity | 5–95% RH, non-condensing (IEC 60068-2-78) | |
| Cooling Method | Forced air (internal fan + cabinet ventilation required) | |
| Dimensions (W×H×D) | 276 × 602 × 353 mm (10.9 × 23.7 × 13.9 in) | |
| Net Weight | ~68 kg (150 lb) | Frame E0 typical |
| PCB Protection | Coated PCBs (standard for harsh industrial use) | |
| Vibration Resistance | 5–150 Hz, 0.5 g (IEC 60068-2-6) |
4. Protection & Functional Safety
| Feature | Specification |
|---|---|
| Overcurrent Protection | I²t monitoring, instantaneous short-circuit shutdown |
| Overvoltage/Undervoltage | DC link voltage monitoring with auto-recovery |
| Overtemperature | IGBT, heatsink, and motor thermal protection (PTC/KTY input) |
| Short-Circuit/Earth Fault | Fast detection (<10 µs) and safe shutdown |
| Safe Torque Off (STO) | SIL 3 / Cat. 3 / PL d (EN ISO 13849-1, IEC 61508) |
| Emergency Stop | Implemented via STO (no contactor required) |
| Motor Protection | I²t thermal model, stall protection, phase loss detection |
5. I/O & Communication Interfaces
| Interface | Details |
|---|---|
| Control Unit | Built-in (frame E0); ACS-CP-U operator panel (standard) |
| Analog Inputs (AI) | 2 × 0–10 V / 4–20 mA (isolated, 12-bit) |
| Analog Outputs (AO) | 2 × 0–10 V / 4–20 mA (isolated, 12-bit) |
| Digital Inputs (DI) | 6 × 24 V DC (isolated, configurable) |
| Digital Outputs (DO) | 3 × Relay / NPN/PNP (isolated, configurable) |
| Encoder Interface | HTL/TTL (FEN-01), Sin/Cos (FEN-11) – optional modules |
| Built-in Communication | Modbus RTU (RS-485) |
| Optional Fieldbuses | PROFIBUS DP (FPBA-01), PROFINET/FENA-11, EtherNet/IP, CANopen (FCAN-01) |
6. Motor Compatibility & Application Data
| Item | Specification |
|---|---|
| Supported Motors | Induction (IM), Permanent Magnet (PMSM), Synchronous Reluctance (SynRM) |
| Duty Cycle | S1 (continuous) – HD/LD rated |
| Braking Options | External brake chopper (optional for frame E0); external brake resistor required |
| Typical Applications | Extruders, cranes, winders, conveyors, mixers, pumps, fans |
| Suitable Industries | Plastics, metals, material handling, food & beverage, textile, paper converting |
Key Notes for Selection
- Current Matching: Ensure motor rated current ≤ 290 A (HD) or ≤ 290 A (LD) for reliable operation.
- Derating: Altitude >1000 m or temperature >40 °C requires output current derating (follow ABB DriveSize tool).
- Accessories: Frame E0 requires external brake chopper for dynamic braking; communication modules are field-installable.