This datasheet specifies the ABB ACS880-01-12A6-3+E200+J425, a wall-mounted IP21 AC drive (R6 frame) for 3-phase 380–415V systems, featuring DTC control, integrated STO, EMC filter (E200), and Modbus RTU communication (J425)ABB Group.
Model Breakdown
- Base Model: ACS880-01-12A6-3 (5.5kW/12.9A, 400V, wall-mounted IP21 drive, R6 frame)
- Option E200: Integrated EMC filter (Class C2, compliant with EN 61800-3)
- Option J425: Modbus RTU communication interface (RS-485 port)ABB Group
Core Technical Specifications
| Parameter | Value | Unit | Notes |
|---|---|---|---|
| Input Voltage | 380–415 | VAC | 3-phase, 50/60Hz, ±10% tolerance |
| Output Voltage | 0–415 | VAC | 3-phase, variable frequency |
| Rated Output Current (In) | 12.9 | A | Continuous (heavy-duty)ABB Group |
| Rated Power (400V) | 5.5 | kW | Heavy-duty (HD) ratingABB Group |
| Max Output Frequency | 500 | Hz | Standard; up to 1000Hz optional |
| Control Method | DTC (Direct Torque Control) | — | Precise torque/speed control, sensorless or encoder feedback |
| EMC Filter (E200) | Class C2 | — | Integrated, meets EN 61800-3 |
| Communication (J425) | Modbus RTU (RS-485) | — | 9.6–115.2 kbps, 1 master + 31 slaves |
| Safety Function | STO (Safe Torque Off) | — | SIL 3/PL e, EN ISO 13849-1/IEC 61508 |
| Enclosure Protection | IP21 | — | Wall-mounted; IP54/IP55 via cabinet design |
| Frame Size | R6 | — | Wall-mounted, compact design |
| Dimensions (W×H×D) | 155×409×226 | mm | Approx., standard configuration |
| Weight | 6.0 | kg | Approx., with options |
| Cooling | Forced air | — | Internal fan, bottom intake/top exhaust |
Key Features
- E200 EMC Filter: Reduces conducted emissions, eliminates external filter need, ensures compliance with industrial EMC standards.
- J425 Modbus RTU: Enables seamless integration with PLCs/HMIs; supports standard Modbus register maps for drive monitoring/control.
- DTC Control: Delivers precise torque/speed regulation (0.01Hz speed accuracy, 200% torque at 0Hz); works with induction, PM, and synchronous reluctance motors.
- STO Safety: Prevents unexpected motor startup; certified for SIL 3/PL e applications.
- Built-in Mains Choke: Reduces harmonic distortion; improves power quality and drive reliability.
- I/O Flexibility: 6 DI, 2 DO, 2 AI, 1 AO (expandable via FIO modules); supports encoder feedback (HTL/TTL).
- Energy Optimization: Built-in energy calculator tracks consumption, CO₂ savings, and operational costs.
- Serviceability: Removable control unit, USB port on ACS-AP-I panel for quick commissioning/backup.
Safety & Compliance
- Standards: IEC 61508 (SIL 3), EN ISO 13849-1 (PL e), EN 61800-5-1, EN 61800-3 (Class C2).
- Protection Features: Overcurrent, overvoltage, undervoltage, overtemperature, short circuit, ground fault, phase loss protection.
- EMC: Complies with EN 61800-3 Class C2 (E200 fitted); meets CE, UL, cUL certificationsABB Group.
Mechanical & Environmental
- Mounting: Wall-mounted (R6 frame); vertical orientation recommended.
- Operating Temperature: -10 to +40°C (derate 1%/°C above 40°C up to 50°C).
- Storage Temperature: -40 to +70°C.
- Humidity: 5–95% (non-condensing).
- Vibration: 0.5g (5–150Hz); 1g (150–1000Hz).
- Altitude: ≤1000m (derate 1%/100m above 1000m up to 4000m).
Ordering & Documentation
- Order Code: ACS880-01-12A6-3+E200+J425
- ABB Part Number: 3ABD00035964-D (base)+E200+J425ABB Group
- Certifications: CE, UL, cUL, TÜV Nord (safety).
- Manuals:
- Hardware Manual: 3AXD50000010106 (ACS880-01+E200+J425)
- Safety Manual: ACS880 Functional Safety Guide
- EMC Guide: ACS880 EMC Compliance Manual
- Communication Guide: Modbus RTU Interface for ACS880 Drives
Application Areas
- General Industry: Pumps, fans, conveyors, mixers, and compressors requiring precise speed control and energy efficiency.
- Material Handling: Light-duty conveyors, packaging machines, and small material processing systems.
- OEM Machinery: Textile, printing, and food processing equipment needing compact, cost-effective drives with communication capabilities.