This datasheet details the ABB ACS880-04-370A-7, a 3-phase open-chassis drive module with 370A output current and 355kW (476HP) rating at 690V, integrating Direct Torque Control (DTC) for precise industrial motor control, suitable for pumps, fans, conveyors, and compressorsABB Group.
General Information
| Item | Specification |
|---|---|
| Model Number | ACS880-04-370A-7 |
| Product Family | ACS880 Series |
| Ordering Code | 3AUA0000161801 |
| Frame Size | R10 |
| Mounting Type | Floor-standing, open chassis (IP20) |
| Enclosure Protection | IP20 (UL Open Type) |
| Control Panel | Assistant Bluetooth (optional) |
| Standard Feature | Built-in choke for harmonic filtering |
Electrical Ratings
| Parameter | Value |
|---|---|
| Input Voltage | 3-phase, 525-690V AC (690V nominal), 50/60Hz |
| Output Voltage | 3-phase, 0-Input Voltage, 0-500Hz (adjustable via control mode) |
| Output Current (Normal Duty) | 370A (355kW/476HP at 690V) |
| Output Current (Heavy Duty) | 325A (315kW/422HP at 690V) |
| Output Current (Light Overload) | 360A (355kW/476HP at 690V) |
| Overload Capacity | 150% for 1 minute, 110% for continuous |
| Efficiency | >98% (at rated load) |
| Power Factor | >0.98 (at rated load) |
| Power Dissipation | 5980W |
| Standby Loss | 402W |
Mechanical Dimensions & Weight
| Dimension | Value |
|---|---|
| Height | 1540 mm (60.63 in) |
| Width | 520 mm (20.47 in) |
| Depth | 478 mm (18.82 in) |
| Net Weight | 295 kg (650 lbs) |
Communication & Control
| Feature | Specification |
|---|---|
| Control Method | Direct Torque Control (DTC) |
| Standard Protocols | Modbus RTU (built-in); PROFIBUS DP, Ethernet/IP (optional) |
| I/O Configuration | 6 digital inputs, 3 relay outputs, 2 analog inputs, 2 analog outputs (configurable) |
Protection & Safety
| Protection Feature | Description |
|---|---|
| Overcurrent Protection | Trips when output current exceeds the set threshold |
| Overvoltage Protection | Activates when DC bus voltage is overly high |
| Undervoltage Protection | Triggers when input voltage is below the minimum limit |
| Overtemperature Protection | Shuts down the drive if heatsink temperature is too high |
| Short Circuit Protection | Protects against output short circuits |
| STO Function | Safe Torque Off (SIL3 as per IEC61511, SILCL3 as per IEC62061, PLe ISO13849-1) |
Environmental Conditions
| Condition | Range |
|---|---|
| Operating Temperature | -15°C to +40°C (5°F to 104°F); derate 1% per 10°C above 40°C |
| Storage Temperature | -40°C to +70°C (-40°F to 158°F) |
| Relative Humidity | 5% to 95% (non-condensing) |
| Altitude | Up to 1000m (3300ft) without derating; derate 1% per 100m above 1000m |
| Vibration | 0.5g (5Hz to 150Hz) |