ACS880-04-370A-7 PN: 355KW, IN: 370A

Part Number: ACS880-04-370A-7
Manufacturer Brands: ABB
Place of Originr: Made in Finland
Net Weight: 161 kg

Inquire this item

EurAutomation.com is a professional supplier of industrial automation products, providing integrated solutions, such as PLC, HMI, CNC, DRIVES, CNC, INVERTER, VFDs, frequency converter cabinet, DC speed control cabinet, widely used in industrial automation, process automation, humanoid robots, intelligent factories, unmanned workshops, no matter what your procurement needs are, you only need to send an email. We will serve you as soon as possible.
This datasheet details the ABB ACS880-04-370A-7, a 3-phase open-chassis drive module with 370A output current and 355kW (476HP) rating at 690V, integrating Direct Torque Control (DTC) for precise industrial motor control, suitable for pumps, fans, conveyors, and compressorsABB Group.

General Information

Item Specification
Model Number ACS880-04-370A-7
Product Family ACS880 Series
Ordering Code 3AUA0000161801
Frame Size R10
Mounting Type Floor-standing, open chassis (IP20)
Enclosure Protection IP20 (UL Open Type)
Control Panel Assistant Bluetooth (optional)
Standard Feature Built-in choke for harmonic filtering

Electrical Ratings

Parameter Value
Input Voltage 3-phase, 525-690V AC (690V nominal), 50/60Hz
Output Voltage 3-phase, 0-Input Voltage, 0-500Hz (adjustable via control mode)
Output Current (Normal Duty) 370A (355kW/476HP at 690V)
Output Current (Heavy Duty) 325A (315kW/422HP at 690V)
Output Current (Light Overload) 360A (355kW/476HP at 690V)
Overload Capacity 150% for 1 minute, 110% for continuous
Efficiency >98% (at rated load)
Power Factor >0.98 (at rated load)
Power Dissipation 5980W
Standby Loss 402W

Mechanical Dimensions & Weight

Dimension Value
Height 1540 mm (60.63 in)
Width 520 mm (20.47 in)
Depth 478 mm (18.82 in)
Net Weight 295 kg (650 lbs)

Communication & Control

Feature Specification
Control Method Direct Torque Control (DTC)
Standard Protocols Modbus RTU (built-in); PROFIBUS DP, Ethernet/IP (optional)
I/O Configuration 6 digital inputs, 3 relay outputs, 2 analog inputs, 2 analog outputs (configurable)

Protection & Safety

Protection Feature Description
Overcurrent Protection Trips when output current exceeds the set threshold
Overvoltage Protection Activates when DC bus voltage is overly high
Undervoltage Protection Triggers when input voltage is below the minimum limit
Overtemperature Protection Shuts down the drive if heatsink temperature is too high
Short Circuit Protection Protects against output short circuits
STO Function Safe Torque Off (SIL3 as per IEC61511, SILCL3 as per IEC62061, PLe ISO13849-1)

Environmental Conditions

Condition Range
Operating Temperature -15°C to +40°C (5°F to 104°F); derate 1% per 10°C above 40°C
Storage Temperature -40°C to +70°C (-40°F to 158°F)
Relative Humidity 5% to 95% (non-condensing)
Altitude Up to 1000m (3300ft) without derating; derate 1% per 100m above 1000m
Vibration 0.5g (5Hz to 150Hz)

 