Such: Siemens 6SL3120... ...

Sales03@aotewell.com
Mob/WhatsAPP: +86-133-6088-4385

DCS800-S02-0520-04 DC drive 400 V AC, 50/60 Hz 208 kW

Part Number: DCS800-S02-0520-04
Manufacturer Brands: ABB
Place of Originr: Made in Germany

Inquire this item

EurAutomation.com is a professional supplier of industrial automation products, providing integrated solutions, such as PLC, HMI, CNC, DRIVES, CNC, INVERTER, VFDs, frequency converter cabinet, DC speed control cabinet, widely used in industrial automation, process automation, humanoid robots, intelligent factories, unmanned workshops, no matter what your procurement needs are, you only need to send an email. We will serve you as soon as possible.
Model Definition:
  • DCS800: DC drive series
  • S02: 3‑phase, 4‑quadrant (4‑Q, anti‑parallel bridge) converter module
  • 0520: Rated DC output current = 520 A DC
  • 04: Rated AC input voltage range = 230…400 V AC

1. Power & Electrical Ratings (400 V AC, 50/60 Hz)

Parameter Value Notes
Rated AC Input Voltage 3‑phase, 230–400 V AC ±10% continuous, ±15% short‑term
Input Frequency 50/60 Hz ±2% static tolerance
Rated DC Output Current (Idc) 520 A DC Continuous, IP00, Ta ≤ 40°C
DC Output Voltage (Ud) Max 400 V DC (4‑Q) Depends on AC input voltage
Rated Output Power (Pout) ~208 kW Calculated: 520 A × 400 V ≈ 208 kW
Input AC Current (Iac) ~426 A Iac ≈ Idc × 0.82
Short‑Circuit Current Rating (SCCR) 65 kA For D1–D4 frame sizes
Overload Capability 150% Idc for 60 s

115% Idc for 15 min

Standard ratings

2. Field Exciter (Internal, Standard)

Parameter Value
Field Voltage (Uf) Max 110 V DC Selectable via option code
Field Current (If) Max 15 A DC Continuous
Field Power Max 1.65 kW

3. General Specifications

Item Details
Frame Size D4
Protection Class IP00 (open type)
Cooling Forced air
Fan Voltage 230 V AC
Air Flow ~600 m³/h
Power Loss (Ploss) ~5.0 kW At rated load
Ambient Temp 0–40°C (derate above 40°C)
Altitude ≤ 1000 m (derate above)
Control Board SDCS‑DSL‑4 (standard)

4. Control & Interfaces (Standard)

  • Control Panel: DCS800 keypad (mountable on module or cabinet door)
  • I/O: Analog (16‑bit), digital I/O, encoder/tachometer interfaces
  • Communication: Support for PROFIBUS‑DP, Modbus, Ethernet (via option modules)
  • Software: DriveWindow Light 2 (startup, monitoring, parameter setting)

5. Typical Fuse & Line Reactor

  • AC Fuse: 700 A, 660 V (UR OFAX 3 S3 4)
  • Line Reactor: ND10 (for 400 V supply)

Leave a Replay