Note: Your model 1606‑XLX240EE is likely a typo; the correct part number is 1606‑XLE240EE (XLE series, 240W, 24V DC).
1. General & Ordering Information
| Parameter | Value | Unit | Notes |
|---|---|---|---|
| Model | 1606‑XLE240EE | – | Allen‑Bradley / Rockwell Automation |
| Series | 1606‑XLE (Essential Line) | – | DIN‑rail mounted industrial power supply |
| Rated Output Power | 240 | W | Continuous |
| Peak Power | 288 | W | 120% power boost (20% reserve) |
| Type | Single‑output AC‑DC switching power supply | – | For industrial control systems |
2. Input (AC) Specifications
| Parameter | Value | Unit | Notes |
|---|---|---|---|
| Rated Input Voltage | 200…240 | V AC | 50/60 Hz |
| Operating Input Range | 180…264 | V AC | 50/60 Hz (wide range) |
| Input Frequency | 50 / 60 | Hz | ±6% tolerance |
| Rated Input Current | ~1.3 | A | At 240 V AC, full load |
| Inrush Current | Limited by NTC thermistor | – | No external pre‑charge needed |
| Power Factor (PF) | 0.52 (typical) | – | At full load, 240 V AC |
| External Fuse Recommendation | B‑10 A or C‑6 A | – | Primary side (min. rating) |
3. Output (DC) Specifications
| Parameter | Value | Unit | Notes |
|---|---|---|---|
| Rated Output Voltage | 24 | V DC | Factory preset |
| Output Voltage Adjustment Range | 24…28 | V DC | Front‑panel potentiometer |
| Rated Output Current | 10 | A | At 24 V DC, continuous |
| Max. Current (28 V DC) | 8.6 | A | To maintain 240 W power |
| Ripple & Noise | ≤ 150 | mVpp | 20 MHz bandwidth |
| Line Regulation | ≤ 5 | mV | 180…264 V AC input change |
| Load Regulation | ≤ 100 | mV | 0…100% load change |
| Efficiency | ≥ 90 | % | Typical at full load |
| Power Loss | ~22.9 | W | Typical at 240 V AC, full load |
4. Protection Features
| Protection Type | Details |
|---|---|
| Overload Protection (OLP) | 120% (288 W) continuous; hiccup mode, auto‑recovery |
| Short‑Circuit Protection (SCP) | Constant current limiting + auto‑restart |
| Overvoltage Protection (OVP) | 36…39 V DC (latch off, reset by power cycle) |
| OverTemperature Protection (OTP) | Thermal shutdown, auto‑recovery when cooled |
| Reverse Polarity Protection | No (external diode recommended) |
5. Mechanical & Environmental
| Parameter | Value | Unit | Notes |
|---|---|---|---|
| Dimensions (W × H × D) | 60 × 125 × 115 | mm | DIN‑rail mount |
| Weight | ~0.91 | kg | Approx. |
| Mounting | 35 mm DIN rail (EN 60715) | – | Vertical installation |
| Cooling | Natural convection (fanless) | – | Low noise, low maintenance |
| Operating Temperature | 0…+60 | °C | Derate 6 W/°C above 60 °C |
| Storage Temperature | −25…+70 | °C | – |
| Relative Humidity | 5…95 | % | Non‑condensing |
| Protection Class | IP20 | – | For cabinet use only |
| Altitude | ≤ 2000 | m | No derating up to 2000 m |
6. Approvals & Compliance
| Standard | Certification |
|---|---|
| Safety | UL 508, CSA C22.2, TÜV, cULus |
| EMC | CE (EN 61000‑6‑1, EN 61000‑6‑2) |
| Others | C‑TICK, GOST, KC, Marine |