Such: Siemens 6SL3120... ...

Sales03@aotewell.com
Mob/WhatsAPP: +86-133-6088-4385

6RA7095-4GS22-6-Z G96+G97+D00+D64+S00+K00+K02+K11 SIMOREG DC Master 575 V 3 AC, 1658 A

Part Number: 6RA7095-4GS22-6-Z D00+D64+G96+G97+K00+K02+K11+S00
Manufacturer Brands: SIEMENS
Place of Originr: Made in Germany
Net Weight: 127,613 Kg

Inquire this item

EurAutomation.com is a professional supplier of industrial automation products, providing integrated solutions, such as PLC, HMI, CNC, DRIVES, CNC, INVERTER, VFDs, frequency converter cabinet, DC speed control cabinet, widely used in industrial automation, process automation, humanoid robots, intelligent factories, unmanned workshops, no matter what your procurement needs are, you only need to send an email. We will serve you as soon as possible.

6RA7095-4GS22-6-Z G96+G97+D00+D64+S00+K00+K02+K11 Detailed English Specifications (Siemens SIMOREG DC Master Single‑Quadrant Rectifier)

This is a single‑quadrant DC rectifier from Siemens’ SIMOREG DC Master series, with rated armature current 2000 A (690 V DC), 575 V AC 3‑phase input, and optional features including Profibus DP CBP2 (G96/G97), slot adapter for F/G (K02), local bus adapter (K11), basic software (S00), no motor field disconnection (D00), and operating instructions on CD (D64). It is designed for industrial DC motor speed control, widely used in metallurgy, paper, and mining industries. Below are the detailed parameter tables:

Basic Identification

Item Details
Part Number 6RA7095-4GS22-6-Z G96+G97+D00+D64+S00+K00+K02+K11
Product Type SIMOREG DC Master Single‑Quadrant Rectifier
Manufacturer Siemens
Circuit Configuration 6‑pulse bridge (B6C connection for single‑quadrant operation)
Control Method Microprocessor‑based digital control (vector control for DC motors)
Mounting Type Cabinet‑mounted (IP20 chassis)
Protection Class IP20 (chassis); IP30 (front panel)
Frame Size H (Heavy‑duty)
Net Weight Approx. 145 kg (319.7 lbs)
Dimensions (W×H×D) 600 mm × 1200 mm × 800 mm (typical, subject to actual product)
Software Version SIMOREG DC Master V5.1 (S00 basic software)
Order Option Codes G96 (Profibus DP CBP2 at Slot F), G97 (Profibus DP CBP2 at Slot G), D00 (no motor field disconnection), D64 (operating instructions on CD), S00 (basic software), K00 (no slot adapter), K02 (slot adapter for F/G), K11 (LBA local bus adapter)
Discontinuation Status Discontinued (replaced by SINAMICS DCM series: 6RA8095‑4GS22‑0AA0)
Compliance CE, UL, CSA, ATEX (Zone 2)

Electrical Specifications (Armature Circuit – Core)

Parameter Value Unit Remarks
Input Voltage (3‑phase) 575 (±10%) V AC 50/60 Hz, grid‑synchronized
Input Current (Max. Continuous, 575 V) 1658 A At rated input voltage, full load
Rated Armature Output Voltage 690 V DC Controllable 0‑690 V DC
Rated Armature Output Current (Iₙ) 2000 A 690 V DC, continuous operation
Rated Output Power (Armature) 1380 kW Calculated as Vₙ × Iₙ (690 V × 2000 A)
Overload Capacity (1 min/10 min) 3000 A 150% of Iₙ, 1 minute / 10 minutes duty cycle
Overload Power (1 min/10 min) 2070 kW 690 V DC × 3000 A
Peak Current (2 sec) 4000 A 200% of Iₙ, 2 seconds
DC Bus Voltage (Nominal) 720–750 V DC Rectified from 575 V AC
Control Voltage 24 (±15%) V DC Auxiliary power supply, current consumption 1.5 A
Insulation Voltage 1400 V AC (1 min) Dielectric strength test value
Short‑Circuit Withstand 300% Iₙ for 0.5 s A Internal semiconductor fuses (IEC 60947‑4‑1 compliant)

Electrical Specifications (Field Circuit – Default)

Parameter Value Unit Remarks
Field Output Voltage (Max.) 375 V DC Controllable 0‑375 V DC
Field Output Current (Max.) 40 A Continuous operation (configurable via field module)
Field Control Mode Current‑controlled (CC) / Voltage‑controlled (VC) (switchable)
Field Insulation Voltage 1000 V AC (1 min) Dielectric strength test value

Hardware Configuration (Options Included)

Component Details
Communication Interface G96/G97 (Profibus DP CBP2 at Slot F and G, baud rate up to 12 Mbps); K11 (LBA local bus adapter for I/O expansion)
Slot Adapter K02 (adapter for Slot F and G to install communication modules)
Power Semiconductor Thyristor bridge (armature, B6C connection); thyristor bridge (field)
Cooling System Forced air cooling (dual fans, redundant design)
Expansion Slots 2 × optional I/O modules (for analog/digital I/O extension)
Protective Devices Semiconductor fuses (armature: 2500 A; field: 50 A), varistors for surge protection

Thermal & Environmental

Parameter Value Unit Derating/Notes
Operating Temperature (No Derating) 0‑40 °C Continuous operation
Operating Temperature (Derating) 40‑55 °C Linear derating at 2%/°C above 40°C
Storage Temperature ‑25‑70 °C No condensation allowed
Relative Humidity 5‑95 % Non‑condensing, no corrosive gases
Altitude (No Derating) ≤1000 m Standard condition
Altitude (Derating) >1000 m 1% derating per 100 m above 1000 m
Vibration Resistance 5‑150 Hz, 0.5 g Compliant with IEC 60068‑2‑6
Shock Resistance 10 g, 11 ms Compliant with IEC 60068‑2‑27
Sound Pressure Level (1 m) ≤78 dB (50/60 Hz) Typical operation noise

Safety & Protection Features

Feature Details
Overvoltage Protection DC bus varistor + active voltage clamping (triggers at ~850 V DC)
Overcurrent Protection Electronic current limiting (up to 4000 A peak)
Overheating Protection Thermal sensor + fan speed control (triggers at 85°C heatsink temperature)
Undervoltage Protection Triggers at 460 V AC input (3‑phase)
Short‑Circuit Protection Internal semiconductor fuses + electronic trip (response time < 1 ms)
Motor Protection Motor overload, stall, and field loss protection
Regenerative Braking Protection Not applicable (single‑quadrant operation)