Basic Information
0005-4050-430 is the LCD panel/keyboard assembly for Siemens SIMATIC C7-613 (Model: 6ES7613-1CA02-0AE3), which is a supporting component of this compact control unit. Its electrical parameters are fully consistent with the control unit.
Power Supply Specifications
|
Parameter Item
|
Detailed Specification
|
|
Rated Supply Voltage
|
24V DC
|
|
Allowable Supply Voltage Range
|
20.4V DC (lower limit) ~ 28.8V DC (upper limit)
|
|
Rated Current Consumption
|
700mA
|
|
Typical Idle Current Consumption
|
150mA
|
|
Typical Inrush Current
|
11A
|
|
Inrush Energy (I²t)
|
0.7A²·s
|
|
Typical Power Consumption
|
14W
|
Digital Input Specifications
|
Parameter Item
|
Detailed Specification
|
|
Rated Input Voltage
|
24V DC
|
|
Voltage Range for Signal “0”
|
-3V ~ +5V
|
|
Voltage Range for Signal “1”
|
+15V ~ +30V
|
|
Typical Input Current for Signal “1”
|
9mA
|
|
Input Delay (at rated voltage)
|
Parameterizable (0.1/0.3/3/15ms), default 3ms
|
|
Maximum Connection Cable Length
|
Shielded cable: 1000m; Unshielded cable: 600m (general scenarios); Shielded cable: 100m (technical function scenarios)
|
Digital Output Specifications
|
Parameter Item
|
Detailed Specification
|
|
Rated Output Voltage
|
24V DC
|
|
Rated Output Current for Signal “1”
|
500mA
|
|
Output Current Range for Signal “1”
|
5mA ~ 0.6A
|
|
Minimum Load Current
|
5mA
|
|
Maximum Residual Current for Signal “0”
|
0.5mA
|
|
Total Output Current per Group (at 40℃)
|
3A
|
|
Total Output Current per Group (at 60℃)
|
2A
|
|
Maximum Switching Frequency
|
Resistive load: 100Hz; Inductive load: 0.5Hz; Lamp load: 100Hz; Pulse output: 2.5kHz
|
|
Maximum Connection Cable Length
|
Shielded cable: 1000m; Unshielded cable: 600m
|
Analog Input Specifications
|
Parameter Item
|
Detailed Specification
|
|
Number of Channels
|
4 regular channels + 1 integrated channel
|
|
Allowable Voltage for Current Input (permanent)
|
2.5V
|
|
Destruction Limit for Voltage Input
|
30V (permanent)
|
|
Destruction Limit for Current Input
|
50mA (permanent)
|
|
Input Range
|
Voltage: 0\+10V, -10V\+10V; Current: 0\20mA, -20mA\+20mA, 4mA~20mA; Resistance: 0~600Ω; Resistance thermometer: Pt100
|
|
Input Resistance
|
0\10V/-10\+10V: 100kΩ; 0\20mA/-20\+20mA/4~20mA: 50Ω; Pt100/0~600Ω: 10MΩ
|
|
Conversion Time (per channel)
|
1ms
|
|
Temperature Error (relative to input range)
|
±0.006%/K
|
|
Repeatability (steady state at 25℃)
|
±0.06%
|
|
Maximum Connection Cable Length
|
Shielded cable: 100m
|
Analog Output Specifications
|
Parameter Item
|
Detailed Specification
|
|
Number of Channels
|
2
|
|
Short-circuit Current for Voltage Output
|
Max. 55mA
|
|
No-load Voltage for Current Output
|
Max. 17V
|
|
Output Range
|
Voltage: 0\+10V, -10V\+10V; Current: 0\20mA, -20mA\+20mA, 4mA~20mA
|
|
Load Requirements
|
Voltage output: Minimum 1kΩ resistive load, maximum 0.1μF capacitive load; Current output: Maximum 300Ω resistive load, maximum 0.1mH inductive load
|
|
Output Ripple (0~50kHz bandwidth)
|
±0.1% (relative to output range)
|
|
Linearity Error
|
±0.15% (relative to output range)
|
|
Temperature Error (relative to output range)
|
±0.01%/K
|
|
Repeatability (steady state at 25℃)
|
±0.06%
|
Other Specifications
|
Parameter Item
|
Detailed Specification
|
|
Isolation Voltage
|
Between different circuits: 75V DC/60V AC; Between MANA and M: 75V DC/60V AC
|
|
Insulation Test Voltage
|
500V DC
|
|
Dimensions (Width × Height × Depth)
|
215mm × 165mm × 79.3mm
|
|
Weight
|
915g
|
|
Operating Temperature Range
|
0~40℃ (normal operation); Max. 60℃ (derated operation)
|
|
Storage Temperature Range
|
-40℃ ~ +85℃
|
|
Protection Class
|
IP20 (front panel)
|