Such: Siemens 6SL3120... ...

Sales03@aotewell.com
Mob/WhatsAPP: +86-133-6088-4385

6SL3224-0BE38-8UA0 SINAMICS G120 PM240 Power Module 380-480 V 3 AC +10/-10% 47-63 Hz

Part Number: 6SL3224-0BE38-8UA0
Manufacturer Brands: SIEMENS
Place of Originr: Made in Germany
Net Weight: 51,5 Kg

Inquire this item

EurAutomation.com is a professional supplier of industrial automation products, providing integrated solutions, such as PLC, HMI, CNC, DRIVES, CNC, INVERTER, VFDs, frequency converter cabinet, DC speed control cabinet, widely used in industrial automation, process automation, humanoid robots, intelligent factories, unmanned workshops, no matter what your procurement needs are, you only need to send an email. We will serve you as soon as possible.
This is the complete English technical specification sheet for Siemens 6SL3224-0BE38-8UA0 SINAMICS G120 PM240 power module, covering core electrical ratings, performance, protection, mechanical/environmental data, and functional details, based on Siemens official documentation and certified industrial catalogs.

1. Core Electrical Specifications

Parameter Value Unit Notes
Product Model 6SL3224-0BE38-8UA0 SINAMICS G120 PM240 power module, unfiltered with integrated braking chopper
AC Input (3‑phase) 380–480 (rated: 400) V AC 3‑phase, 50/60 Hz, (+10%/-10% tolerance)
AC Input Frequency 47–63 Hz Grid frequency range
DC Bus Voltage 510–750 V DC Operating voltage for power module
Rated Output Current (LO, 0–40°C) 205 A Low overload (LO): 110 kW continuous
Rated Output Current (HO, 0–50°C) 178 A High overload (HO): 90 kW continuous
Maximum Output Current 308 (150% of LO rated) A For 3s, with 10‑minute cool‑down interval
Rated Output Power (LO) 110 (150 hp) kW At 0–40°C ambient, 400 V rated voltage
Rated Output Power (HO) 90 (125 hp) kW At 0–50°C ambient, 400 V rated voltage
Output Voltage 0–480 V AC Matches input voltage (95% of input voltage)
Output Frequency 0–550 (V/F); 0–240 (vector) Hz Frequency range based on control mode
Pulse Frequency 2 (adjustable up to 16) kHz Default 2 kHz; adjustable via control unit
Braking Chopper Integrated For dynamic braking; requires external braking resistor
Power Factor (λ) 0.85 At rated load
Offset Factor (cos φ) 0.95 Power factor correction factor
Efficiency (η) 0.97 At rated load

2. Overload Capabilities

Overload Condition Current Duration Ambient Temperature
LO (110 kW) 308 A (150% of rated) 3 s 0–40°C
LO (110 kW) 225.5 A (110% of rated) 57 s 0–40°C
LO (110 kW) 205 A (100% of rated) 240 s 0–40°C
HO (90 kW) 284.8 A (160% of rated) 3 s 0–50°C
HO (90 kW) 242.1 A (136% of rated) 57 s 0–50°C
HO (90 kW) 178 A (100% of rated) 240 s 0–50°C

3. Performance & Protection Specifications

Parameter Value Unit Notes
Control Modes V/F, vector (sensorless/encoder) Supports both control types for motor control flexibility
Current Control Accuracy ±0.5% of rated current Closed‑loop current regulation
Overcurrent Protection 200% of rated current Instantaneous trip to prevent device damage
Overvoltage Protection 800 V DC Active clamping via bus capacitor/discharge circuit
Undervoltage Protection 480 V DC Shuts down to prevent IGBT damage
Overheating Protection 85 °C Heatsink temperature threshold; fan speed control + alarm/trip
Short‑circuit Protection Internal fast‑acting fuses Coordinated with power section design
EMC Compliance EN 61800‑3, Category C2 Suitable for industrial environments (unfiltered; filter optional)

4. Mechanical & Environmental Specifications

Parameter Value Unit Notes
Cooling Method Forced air cooling Integrated fan with speed monitoring
Cooling Air Requirement 0.150 m³/s Airflow for internal cooling
Net Weight 38 kg Base unit without packaging
Dimensions (H×W×D) 634×350×316 mm Standard frame size FSF
Ambient Temperature 0–40 (LO); 0–50 (HO) °C Operating; derate 1% per 100 m above 1000 m altitude
Storage/Transport Temperature −25 to +70 °C
Installation Altitude ≤1000 m Derate 1% per 100 m above 1000 m
Relative Humidity 5–95% % Non‑condensing
Vibration Resistance 0.5 g 10–150 Hz, IEC 60068‑2‑6
Shock Resistance 15 g 11 ms, IEC 60068‑2‑27
IP Rating IP20 Enclosure protection class
Sound Pressure Level (1m) 65 dB Under standard operating conditions

5. Key Functional & Compliance Details

  • Braking Chopper: Integrated for dynamic braking; requires external braking resistor (rated 150 kW for 3s) for high‑deceleration applications.
  • Control Compatibility: Works with SINAMICS G120 control units (CU240B‑2, CU240E‑2) for V/F or vector control modes.
  • Compliance: RoHS directive compliant; meets IEC 61800‑3, NEMA ICS 1.1, and UL 508C standards.
  • Typical Applications: Heavy‑duty industrial applications such as pumps, conveyors, fans, compressors, and material handling systems requiring precise speed/torque control.

6. Supplementary Notes

  1. Overload Limitation: LO (110 kW) and HO (90 kW) ratings are temperature‑dependent; ensure ambient temperature stays within specified ranges to avoid thermal damage.
  2. Braking Resistor: External braking resistor must be sized according to the application’s braking power requirements; refer to Siemens G120 Braking Resistor Selection Guide for details.
  3. Documentation: Refer to Siemens SINAMICS G120 Power Module PM240 Manual (Document No. 6SL3200‑0BE38‑8UA0) for complete parameterization and troubleshooting.

Leave a Replay