- Order No.:6SL3130-1TE24-0AA0
- Product Family:SINAMICS S120 Basic Line Module (Booksize frame)
- Core Function:Non-regenerative AC-to-DC rectifier; supplies stable DC link voltage for S120 motor modules; internal air cooling; includes DRIVE-CLiQ cable; no regenerative braking (energy exchange via DC link only)
- Input:3AC 380–480 V, 50/60 Hz
- Output:DC 600 V (nominal), 67 A rated current, 40 kW rated power
- Cooling:Internal air cooling (integral fan)
- Enclosure:IP20 (open chassis, booksize format)
- Certifications:CE, UL, CUL, RoHS compliant
- Country of Origin:Germany
- Net Weight:~15 kg (33.07 lbs) (refer to full datasheet for exact value)
Key Technical Specifications (English)
| Parameter | Value |
|---|---|
| Rated Input Voltage | 3AC 380–480 V, 50/60 Hz |
| Rated DC Output Voltage | 600 V DC (nominal); operating range ~510–650 V DC |
| Rated DC Output Current | 67 A |
| Rated Power | 40 kW (at 400 V AC input) |
| Auxiliary Power Supply | 24 V DC (-15% / +20%) |
| Frame Size | Booksize (compact, rack-mountable) |
| Cooling Type | Internal air cooling (built-in fan) |
| Operating Temperature | 0 … +40 °C (no derating up to 1000 m); derate linearly above 40 °C |
| Storage Temperature | -25 … +70 °C |
| Relative Humidity | 5 … 95% (non-condensing) |
| Installation Altitude | Up to 2000 m (derating above 1000 m) |
| Communication | DRIVE-CLiQ (integrated, for control unit connection) |
| Safety Features | Overvoltage/overcurrent/overtemperature protection; no integrated STO (STO via motor modules/control unit) |
| Compliance | EN 61800‑3, IEC 60947-6-2, UL 508C, CSA C22.2 No. 14 |
| Harmonic Performance | Basic rectifier (higher THDi vs Active Line Module; meets basic EMC standards for industrial use) |
Download & Usage Notes
- Set language to English (top-right corner) on Siemens Industry Mall to access English-only documents.
- Download the full PDF datasheet for complete details: exact dimensions, derating curves, EMC guidelines, wiring diagrams, M-CAD/E-CAD (STEP/DXF), firmware compatibility, and safety instructions.
- Pair with SINAMICS S120 Control Unit (e.g., CU320-2 series) and Motor Modules (e.g., 6SL3120 series) for complete drive system; use external braking resistor (if needed) for energy dissipation (no regeneration to grid).
- Verify the latest revision date for project compliance and technical accuracy.
- Use STARTER or TIA Portal software for configuration, commissioning, and diagnostics.