Product Overview
6SL3210-1PE27-5AL0 is a SINAMICS G120 PM240-2 power module (IP20, FSD frame) with built-in Class A EMC filter and integrated braking chopper. It runs on 3-phase 380–480 V AC input, supports high overload (HO) 30 kW and low overload (LO) 37 kW ratings, and requires a separate control unit (e.g., CU240E‑2 PN/DP) for full drive operation.
Key Electrical & Mechanical Data
| Parameter | Value |
|---|---|
| Product Type | Power Module PM240-2 (SINAMICS G120) |
| Input | 3‑phase AC, 380–480 V ±10%, 47–63 Hz |
| Rated Output Power (HO) | 30 kW (200% overload 3 s, 150% 57 s, 100% 240 s; -20…+50 °C) |
| Rated Output Power (LO) | 37 kW (150% overload 3 s, 110% 57 s, 100% 240 s; -20…+40 °C) |
| Rated Input Current (LO) | 70.0 A |
| Rated Input Current (HO) | 62.0 A |
| Built‑in Features | Class A EMC filter, integrated braking chopper |
| IP Rating | IP20 / UL open type |
| Frame Size | FSD |
| Dimensions (H×W×D) | 472 × 200 × 237 mm |
| Net Weight | 18.5 kg (40.79 lb) |
| Max. Output Frequency | Up to 550 Hz (depends on motor & application) |
| Ambient Operating Temp (HO) | -20 … +50 °C (derate above 40 °C) |
| Ambient Operating Temp (LO) | -20 … +40 °C |
| Storage Temp | -40 … +70 °C |
| Humidity | 5 … 95% RH (non‑condensing) |
| Cooling | Forced air cooling |
| Commodity Code | 85044090 |
| Lifecycle Status | Active |
| Firmware Requirement | CU firmware V4.7 HF8 or later |
| Country of Origin | Germany |
Compliance & Certifications
- CE: Conforms to EMC and LVD directives
- RoHS: Compliant
- WEEE (2012/19/EU): Compliant
- REACH: No SVHC reported (as of 2026‑01‑26)
- UL/cUL: Recognized (open type)
Critical Notes
- This is a power module only—requires a separate control unit (CU) and optional operator panel for full functionality.
- Built‑in Class A filter suits industrial environments; for residential/light commercial, use Class B filter or external EMC solutions.
- Integrated braking chopper supports dynamic braking; add external braking resistor for energy dissipation.
- Do not exceed 480 V AC input; overvoltage damages power semiconductors and DC link.
- For full wiring, dimensioning, cooling, safety, and parameterization, refer to the complete PDF datasheet and SINAMICS G120 Operating Instructions.