Such: Siemens 6SL3120... ...

Sales03@aotewell.com
Mob/WhatsAPP: +86-133-6088-4385

6GK1415-2AA00 SIMATIC NET, DP/AS-INTERFACE LINK

6GK1415-2AA00 is discontinued IP20 PROFIBUS DP/AS-i V2.1 gateway, DIN rail mount, AS-i bus powered, for S7-300/400 fieldbus signal conversion.
Alternate PN: 6GK14152AA00
Manufacturer Brands: SIEMENS
Place of Originr: Made in Germany

Inquire this item

6GK1415-2AA00 is discontinued IP20 PROFIBUS DP/AS-i V2.1 gateway, DIN rail mount, AS-i bus powered, for S7-300/400 fieldbus signal conversion.

SIMATIC NET, DP/AS-INTERFACE LINK 20 GATEWAY PROFIBUS DP/AS-INTERFACE DEGREE OF PROTECTION IP20

Parameter Item Official Specification Value
Full Market Article Number 6GK1415-2AA00
Full Product Name SIMATIC NET DP/AS-INTERFACE LINK 20 Gateway, PROFIBUS DP / AS-Interface Converter
Product Series SIMATIC NET AS-i & PROFIBUS Communication Gateway Module
Core Function Bidirectional protocol conversion between PROFIBUS DP master and AS-Interface fieldbus
Protection Class IP20 (finger-safe, for cabinet internal installation only)
Supported AS-i Standard AS-Interface Specification V2.1
PROFIBUS Interface 1 × RS485 9-pin Sub-D PROFIBUS DP port, operates as PROFIBUS DP slave
AS-i Connection Port 1 × screw-type terminal AS-Interface bus port
Power Supply Mode Powered entirely via AS-i profile cable, no separate 24VDC external supply required
Max Current Consumption 200 mA drawn from AS-i bus (30V AS-i nominal voltage)
Power Loss Max 4.5 W
Supported PROFIBUS Modes DPV0, DPV1
Max AS-i Nodes Capacity Supports 31 standard AS-i slaves, total 496 digital I/O points
Address Setting Method Front panel rotary DIP switches for PROFIBUS station address
Mounting Type Standard DIN rail TS35 mounting
Operating Temperature (Horizontal Mount) 0 °C to +45 °C
Operating Temperature (Vertical Mount) 0 °C to +60 °C
Storage / Transport Temperature -40 °C to +70 °C
Relative Humidity Max 95% non-condensing at 25°C
Compatible PLC Controllers SIMATIC S7-300, S7-400, WinAC with PROFIBUS DP interface
Engineering Software Requirement STEP7 V5.1 SP2 or higher, GSD file integrated
Diagnostic Indicators Front LED status lights for PROFIBUS, AS-i bus fault and power status
Safety Protocol Support No ASIsafe / PROFIsafe safety function support
Product Lifecycle Status PM410: Discontinued legacy product, superseded by 6GK1415-2AA10 (Link 20E V3.0)
Compliance Certifications CE, RoHS, WEEE industrial compliance
Export Control Classification ECCN EAR99, no restricted export limits
Origin Czech Republic