7UM6211-6EB91-0AA0/FF Multifunction Generator, Motor & Transformer Protection Relay

7UM6211‑6EB91‑0AA0/FF
Alternate PN: 7UM62116EB910AA0
Manufacturer Brands: SIEMENS
Place of Originr: Made in Germany

Inquire this item

7UM6211‑6EB91‑0AA0/FF

Siemens SIPROTEC 7UM6211‑6EB91‑0AA0/FF

Multifunction Generator, Motor & Transformer Protection Relay

1. Ordering Code Decoding (Model Breakdown)

Code Segment Value Meaning
7UM62 7UM62 SIPROTEC 4, Multifunction Machine Protection Relay
11 11 Standard function version (generator/motor/transformer)
6 6 1/2 × 19” flush‑mounting, high‑profile housing
E E Plug‑in terminal blocks
B B 5 A CT rated current (low sensitivity)
91 91 Firmware variant & hardware revision
0AA0 0AA0 Basic version, no communication, no synchrocheck
/FF /FF Factory configuration, standard testing

2. General Technical Data

Parameter Specification Unit
Manufacturer Siemens AG
Product Series SIPROTEC 4 7UM62
Type Multifunction protection relay
Application Generator, motor, transformer protection
Mounting 1/2 × 19” flush mount
Terminals Plug‑in
CT Rated Current 5 A
VT Rated Voltage 100 / 125 V AC
Frequency 50 / 60 Hz
Operating Temperature −25 … +70 °C
Storage Temperature −40 … +85 °C
Relative Humidity 10 … 95 (non‑condensing) %
Protection Class IP54 (front), IP20 (rear)
Dimensions (W×H×D) 210 × 175 × 155 mm
Weight Approx. 8.2 kg

3. Analog Inputs

Input Quantity Range Accuracy
Current (CT) 8 0 … 20 × In (In=5 A) ±0.5 %
Voltage (VT) 4 0 … 1.2 × Un (Un=100 V) ±0.5 %
Sensitive Current 2 0 … 100 mA ±1.0 %

4. Binary I/O

Type Quantity Rating
Binary Inputs (BI) 7 24/48/110/220 V DC
Binary Outputs (BO) 12 250 V AC / 5 A; 300 V DC / 0.5 A

5. Protection Functions (ANSI Codes)

Function ANSI Availability
Current Differential 87
Stator Earth Fault 59N / 64G
Sensitive Earth Fault 51GN / 64R
Overload (Thermal) 49
Overcurrent (Instantaneous/Time‑delay) 50 / 51
Directional Overcurrent 67
Undervoltage / Overvoltage 27 / 59
Underfrequency / Overfrequency 81U / 81O
Rate‑of‑Frequency‑Change 81R
Overexcitation / Underexcitation 24
Negative Sequence (Unbalanced Load) 46
Breaker Failure 50BF
Rotor Earth Fault 64R
Motor Start Monitoring 48
Motor Restart Inhibit 66

6. Communication & Interfaces

Interface Standard Note
Front Port RS232 For local setting (DIGSI 4)
Rear Port None (0AA0) No communication option
Protocol

7. Power Supply

Type Range Power
DC 110 … 250 V
AC 115 … 230 V
Power Consumption < 20 VA

8. Standards & Approvals

Standard Description
IEC 60255 Protection relays
IEC 61000‑6‑2 / ‑4 EMC immunity / emission
UL 508 Industrial control equipment
CSA C22.2 No. 14 Industrial control equipment

9. Key Features

  • Multifunctional: Integrates generator, motor, and transformer protection in one device.
  • High Accuracy: Precision measurement for current, voltage, frequency, and temperature.
  • Flexible Configuration: CFC (Continuous Function Chart) programmable logic.
  • Robust Design: Wide operating temperature range, high vibration immunity.
  • Local Operation: Front LCD and keypad for setting, monitoring, and fault indication.