Such: Siemens 6SL3120... ...

Sales03@aotewell.com
Mob/WhatsAPP: +86-133-6088-4385

Woodward 8272-683 Digital Controller

Woodward 8272-683 is a digital reference controller that outputs isolated 0–10kHz pulse signals as precise speed setpoints for turbine and engine governors. It provides three adjustable speed presets and dual linear ramp functions, compatible with Woodward 2301 and SPC series. Operating on wide 10–45 VDC power with -40°C to +85°C tolerance, it offers status relay feedback for gensets, marine prime movers and industrial test benches.
Alternate PN: Woodward 8272-683
Manufacturer Brands: B&R
Place of Originr: Made in Germany

Inquire this item

Woodward 8272-683 is a digital reference controller that outputs isolated 0–10kHz pulse signals as precise speed setpoints for turbine and engine governors. It provides three adjustable speed presets and dual linear ramp functions, compatible with Woodward 2301 and SPC series. Operating on wide 10–45 VDC power with -40°C to +85°C tolerance, it offers status relay feedback for gensets, marine prime movers and industrial test benches.

Woodward 8272-683 Digital

Item Specification
Part Number 9907-028 (Rev C / Rev E)
Official Product Name SPM-A Analog Speed & Phase Synchronizer Module
Core Function Generator genset frequency & phase matching for grid/paralleling breaker closing
Input Sensing Voltage 115 / 230 VAC RMS, auto-adaptive
Voltage Tolerance Range ±10% of rated AC input
Supported Grid Frequency 50 Hz / 60 Hz dual universal
Frequency Synchronization Deviation Range ±10% nominal frequency
Static Phase Matching Accuracy ±5 electrical degrees
Max Allowed Phase Deviation Threshold ±10 electrical degrees
Voltage Matching Function Not integrated (speed/phase only control)
Selectable Dwell Match-Up Time 1/8 s, 1/4 s, 1/2 s, 1 s (factory default: 0.5 s)
Power Consumption ≤ 5 W maximum
Built-in Control Output Channels High impedance output, Low impedance output, EPG dedicated output
Compatible Woodward Controllers 2301, 2301A, 2500, EPG, EGA / EGM governor series
Operating Mode Selection OFF, RUN, CHECK, PERMISSIVE four switchable modes
Breaker Contact Resistive Rating 10 A @ 28 VDC; 3 A @ 120 VAC (50/60 Hz)
Operating Temperature Range -45 °C ~ +70 °C
Optimal Stable Working Temp +10 °C ~ +30 °C
Storage & Transit Temperature -45 °C ~ +70 °C
Overall Dimension (W × H × D) 292 mm × 171 mm × 57 mm
Net Unit Weight 1.71 ~ 2.2 kg
Mounting Type Cabinet panel embedded mounting / DIN rail optional
Enclosure Protection Class IP20 (indoor switchgear cabinet installation)
Adjustment Potentiometers Phase Offset, Gain, Stability trimmers on front panel
Fail-Safe Logic Lockout circuit prevents breaker closing under out-of-sync condition
Manufacturing Origin United States
Typical Application Scenarios Diesel/gas generator grid paralleling, multi-genset bus synchronization, marine auxiliary power synchronization, industrial backup power transfer systems